Fuse coordination – Rockwell Automation 592- MCS-E3 Electronic Overload Relay Short Circuit Ratings User Manual
Page 2

Table 4 IEC Short Circuit Ratings per EN60947-4-1
MCS-E3 Cat. No.
Prospective S.C.
current, Ir (A)
Conditional S.C.
current, Iq (A)
Max. voltage (V)
193-EC_B, 592-EC_T
1,000
193-EC_D, 592-EC_C
3,000
193-EC_E, 592-EC_D
5,000
193-EC_F
10,000
193-EC_G
18,000
193-EC_H
30,000
193-EC_Z
1,000
Fuse Coordination
Contactor Cat. No. Max. starter FLC
(A)
Prospective S.C.
current, Ir (A)
Conditional S.C.
current, Iq (A)
Max. voltage
(V)
Type I with
Class J fuse (A)
Type II with
Class J fuse (A)
_B
100-C09
9
20
15
_B
100-C12
12
20
20
_B
100-C16
16
30
30
_B
100-C23
23
40
40
_D
100-C30
30
50
50
_D
100-C37
37
50
50
_D
100-C43
43
70
70
_E
100-C60
60
80
80
_E
100-C72
72
100
100
_E
100-C85
85
5,000
150
150
FF, ZZ
100-D95
95
200
200
FF, ZZ
100-D110
110
200
200
FF, ZZ
100-D140
140
250
250
GF, ZZ
100-D180
180
300
300
GG, ZZ
100-D210
210
400
400
GG, ZZ
100-D250
250
400
400
GG, ZZ
100-D300
300
500
500
HG, ZZ
100-D210
210
400
400
HG, ZZ
100-D250
250
400
400
HG, ZZ
100-D300
300
500
500
JG, ZZ
100-D300
300
500
500
JG, ZZ
100-D420
420
600
600
Contactor Size
Max. starter FLC
(A)
Prospective S.C.
current, Ir (A)
Conditional S.C.
current, Iq (A)
Max. voltage
(V)
Type I with
Class J fuse (A)
Type II with
Class J fuse (A)
00
9
1,000
20
20
0, 1
18, 27
3,000
30
30
2
45
3,000
60
60
3
90
5,000
200
200
592-EC_T
592-EC_C
592-EC_C
592-EC_D
10,000
3,000
100,000
600
100,000
600
MCS-E3 Cat. No.
100,000
690
MCS-E3 Cat. No.
193-EC1
193-EC2
193-EC3
193-EC4
193-EC5
1,000
Table 6 Type 1 and Type II Fuse Coordination with NEMA Contactors
Table 5 IEC Type 1 and Type II Fuse Coordination with Bul. 100-C and 100-D contactors per EN60947-4-1
PN-17757
DIR 10000010791 (Version 03)
Printed in U.S.A.