Rockwell Automation 592- MCS-E3 Electronic Overload Relay Short Circuit Ratings User Manual
Short circuit ratings, Warning
MCS-E3 Cat. No.
Contactor Cat. No. Max. Starter FLC (A) Max available fault
current (A)
Max. voltage (V) Max Class J or
CC fuse (A)
_B
100-C09
9
20
_B
100-C12
12
20
_B
100-C16
16
30
_B
100-C23
23
30
_D
100-C30
30
50
_D
100-C37
37
50
_D
100-C43
43
70
_E
100-C60
60
80
_E
100-C72
72
100
_E
100-C85
85
150
193-EC1
FF, ZZ
100-D95
95
100,000
600
200
193-EC2
193-EC3
193-EC4
193-EC5
FF, ZZ
100-D110
110
200
FF, ZZ
100-D140
140
250
GF, ZZ
100-D180
180
300
GG, ZZ
100-D210
210
400
GG, ZZ
100-D250
250
400
GG, ZZ
100-D300
300
500
HG, ZZ
100-D210
210
400
HG, ZZ
100-D250
250
400
HG, ZZ
100-D300
300
500
JG, ZZ
100-D300
300
500
JG, ZZ
100-D420
420
600
MCS-E3 NEMA Cat. No.
Contactor Size
Max available fault
current (A)
Max. voltage (V)
Circuit breaker / Limiter
R
J
_T
00
100,000
600
---
20
---
240
30
30
FDB 3025/LFB 3070R
_C
0
100,000
480
30
30
FDB 3025/LFB 3070R
600
30
30
---
240
60
100
FDB 3050/LFB 3070R
592-EC1
_C
1
100,000
480
30
50
FDB 3035/LFB 3070R
592-EC2
592-EC3
592-EC5
600
30
50
---
240
100
200
FDB 3100/LFB 3150R
_C
2
100,000
480
60
100
---
600
60
100
---
240
200
350
FDB 3150/LFB 3150R
_D
3
100,000
480
100
200
FDB 3125/LFB 3150R
600
100
200
FDB 3100/LFB 3150R
Max UL fuse (A)
Bulletin 193 / 592 MCS-E3 Electronic Overload Relay
Short Circuit Ratings
To prevent electrical shock, disconnect from power source before installing or servicing.
Select the motor branch circuit protection that complies with the national Electrical Code and any other
governing regional and local codes.
The MCS-E3 overload relay is suitable for use on circuits capable of delivering not more than the RMS symmetrical amperes listed in
the following tables:
Short Circuit Ratings
Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14
Table 2 High fault short circuit ratings per UL 508 and CSA 22.2 no. 14 with 100-C and 100-D contactors
Table 3 High fault short circuit ratings per UL 508 and CSA 22.2 no. 14 with NEMA contactors
MCS-E3 Cat. No.
Max. available fault
current (A)
Max. voltage (V)
193-EC_B, 592-EC_T
5,000
193-EC_D, 592-EC_C
5,000
193-EC_E, 592-EC_D
10,000
193-EC_F
10,000
193-EC_G
18,000
193-EC_H
42,000
193-EC_Z
5,000
600
WARNING
WARNING
PN-17757
DIR 10000010791 (Version 03)