Rockwell Automation 592- MCS-E3 Electronic Overload Relay Short Circuit Ratings User Manual

Short circuit ratings, Warning

background image

MCS-E3 Cat. No.

Contactor Cat. No. Max. Starter FLC (A) Max available fault

current (A)

Max. voltage (V) Max Class J or

CC fuse (A)

_B

100-C09

9

20

_B

100-C12

12

20

_B

100-C16

16

30

_B

100-C23

23

30

_D

100-C30

30

50

_D

100-C37

37

50

_D

100-C43

43

70

_E

100-C60

60

80

_E

100-C72

72

100

_E

100-C85

85

150

193-EC1

FF, ZZ

100-D95

95

100,000

600

200

193-EC2

193-EC3
193-EC4
193-EC5

FF, ZZ

100-D110

110

200

FF, ZZ

100-D140

140

250

GF, ZZ

100-D180

180

300

GG, ZZ

100-D210

210

400

GG, ZZ

100-D250

250

400

GG, ZZ

100-D300

300

500

HG, ZZ

100-D210

210

400

HG, ZZ

100-D250

250

400

HG, ZZ

100-D300

300

500

JG, ZZ

100-D300

300

500

JG, ZZ

100-D420

420

600

MCS-E3 NEMA Cat. No.

Contactor Size

Max available fault

current (A)

Max. voltage (V)

Circuit breaker / Limiter

R

J

_T

00

100,000

600

---

20

---

240

30

30

FDB 3025/LFB 3070R

_C

0

100,000

480

30

30

FDB 3025/LFB 3070R

600

30

30

---

240

60

100

FDB 3050/LFB 3070R

592-EC1

_C

1

100,000

480

30

50

FDB 3035/LFB 3070R

592-EC2
592-EC3
592-EC5

600

30

50

---

240

100

200

FDB 3100/LFB 3150R

_C

2

100,000

480

60

100

---

600

60

100

---

240

200

350

FDB 3150/LFB 3150R

_D

3

100,000

480

100

200

FDB 3125/LFB 3150R

600

100

200

FDB 3100/LFB 3150R

Max UL fuse (A)

Bulletin 193 / 592 MCS-E3 Electronic Overload Relay
Short Circuit Ratings

To prevent electrical shock, disconnect from power source before installing or servicing.

Select the motor branch circuit protection that complies with the national Electrical Code and any other
governing regional and local codes.

The MCS-E3 overload relay is suitable for use on circuits capable of delivering not more than the RMS symmetrical amperes listed in
the following tables:

Short Circuit Ratings

Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14

Table 2 High fault short circuit ratings per UL 508 and CSA 22.2 no. 14 with 100-C and 100-D contactors

Table 3 High fault short circuit ratings per UL 508 and CSA 22.2 no. 14 with NEMA contactors

MCS-E3 Cat. No.

Max. available fault

current (A)

Max. voltage (V)

193-EC_B, 592-EC_T

5,000

193-EC_D, 592-EC_C

5,000

193-EC_E, 592-EC_D

10,000

193-EC_F

10,000

193-EC_G

18,000

193-EC_H

42,000

193-EC_Z

5,000

600

WARNING

WARNING

PN-17757
DIR 10000010791 (Version 03)