Introduction

The S02 option extends the kW/HP ratings of the standard 160 drive.
In addition, the following function changes have been made. Refer to
the appropriate page for details.

High Speed Stall Prevention –

page 1

Accel/Decel Selection –

page 2

Smartspin Balance Detection (revised) –

page 3

Braking –

page 3

Five Point V/Hz Curve –

page 4

Program Lock Password –

page 6

Relay Output Contacts –

page 6

Important: FRN 7.06 C004 contains additional functionality and

parameter changes over earlier firmware versions. These
changes are indicated by shading in the tables. In addition,
a summary of parameter changes is provided on

page 6

Firmware Changes

High Speed Stall Prevention

The S02 option provides two current limits, compared to one in the
standard drive. Each current limit has definite conditions. The High
Speed Current Limit is used to keep the motor from stalling, while
accelerating toward frequencies above P35 - [Base Frequency]. For
frequencies between base frequency and 150% of base frequency, the
current limit is linearly decreased from P43 - [Low Speed Current Limit]
to P47 - [High Speed Current Limit]. See

Table A

.

Table A
High Speed Stall Prevention Parameters

!

ATTENTION: Use of this Custom Software without full
understanding of the “Firmware Changes” (see below)
could result in unpredictable motor operation and/or
hazardous machine conditions.

Parameter
Number

Parameter Name

Min./Max./Default Description

P43

Low Speed Current Limit 1/180/150 %

This limit is only in effect from
zero to P35 [Base Frequency].

P47

High Speed Current Limit 1/180/150 %

This limit is only in effect above
150% of P35 [Base Frequency].

160 Series C Custom Firmware

S02 Option – FRN 7.06 C004