beautypg.com

Rockwell Automation 440C-CR30-22BBB Guardmaster Software Configurable Safety Relay Quick Start Guide User Manual

Page 31

background image

Rockwell Automation Publication 440C-QS001A-EN-P — January 2014

29

Quick Start Guide

3.

Add the multi-state indicators for the faults.

4.

Press the reset button to get the outputs on.

Create a short-circuit from terminal 0 to terminal 1.

5.

The PanelView C600 will look like this.

Crossfault 12 – a crossfault occurred on terminal 12, which is Input Test Pulse A.

E-STOP OFF – since Input Test Pulse A is used by the e-stop SMF, it turns OFF.

Gate OFF – since Input Test Pulse A is also used by the Gate SMF, it turns OFF.

The fault causes the Output to turn OFF.

Bit 0 for e-stop provides the message on the “At least one circuit shorted to 24V
or another input circuit” when the mouse is moved over the e-stop or Gate SMF
on the CCW.

Remove the short circuit and cycle the e-stop and gate switch. The Guardmaster
440C-CR30 is now ready for the reset button.