Rockwell Automation 800F- DeviceNet Push Button Stations User Manual
Devicenet, Push button stations, E-doc
41063-195
G. Ushakow
N/A
N/A
N/A
1007825
1
DEVICENET
™
PUSH BUTTON STATION
5-18-04
M. Jutz
5-18-04
B. Simon
5-18-04
1
2
BUL. 800F INSTRUCTION SHEET
REVISION
AUTHORIZATION
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
H
A
B
C
D
E
F
G
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
REFERENCE
SHEET
OF
DWG.
SIZE
B
DR.
CHKD.
APPD.
DATE
DATE
DATE
ANGLES:
.XXX:
.XX:
THIS DRAWING IS THE PROPERTY OF
THE ALLEN-BRADLEY CO. INC.
AND MAY NOT BE COPIED, USED OR
DISCLOSED FOR ANY PURPOSE EXCEPT
AS AUTHORIZED IN WRITING BY
THE ALLEN-BRADLEY CO. INC.
LOCATION : MILWAUKEE,
WISCONSIN
U.S.A.
1
2
3
4
5
6
7
8
E-DOC
±
±
±
DeviceNet
™
Push Button Stations
(Catalog Number 800F–)
Specifications
Installation Manual
Important User Information
The illustrations, charts, sample programs and layout examples shown in
this guide are intended solely for purposes of example. Since there are
many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability (to
include intellectual property liability) for actual use based upon the
examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation, and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some
important differences between solid-state equipment and
electromechanical devices that should be taken into consideration when
applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or
in part, without written permission of Allen-Bradley Company, Inc., is
prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
!
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death,
property damage or economic loss.
Attention statements help you to:
•
identify a hazard
•
avoid the hazard
•
recognize the consequences
Important: Identifies information that is critical for successful
application and understanding of the product.
DeviceNet is a trademark of the Open DeviceNet Vendor Association (ODVA).
For More Information
As part of our effort to preserve, protect, and improve our environment,
Allen
–
Bradley is reducing the amount of paper we use. Less paper means
more options for you. In addition to traditional printed publications and
CD
–
ROM versions, we now offer on
–
line manuals with the most
up
–
to
–
date information you can get. We recommend that you read the
related publications listed below before starting up your control system.
Related Publications
Publication Title
Publication Number
How To Get More Information
For
Obtain Information By
Publications in electronic format
• Visiting the Allen–Bradley internet site –
http://www.ab.com/manuals/
• Publication is on RSNetWorx CD–ROM
• Calling your local Allen–Bradley distributor
Publications in printed format
• Visiting the Automation Bookstore at –
http://www.theautomationbookstore.com
• Visiting the Automation Bookstore at –
http://www.theautomationbookstore.com
Manuals in other languages
• To determine the availability of translated
publication, add a 2–letter suffix to the end
of the publication number
(DN-6.7.2DE) or
replace the US or EN in the publication
number (800E-UM002A-FR-P).
French – FR German – DE Italian – IT
Spanish – ES Portuguese – PT Chinese – ZH
Japanese – JA Dutch – NL
800F DeviceNet Push Button Station User Manual
800-UM002A-EN-P
800F Push Button Selection Guide
800F-SG001A-US-P
DeviceNet Cable System Planning and Installation Manual DN-6.7.2
1756-DNB Scanner Module Configuration
1756-6.5.19
RSNetWorx for DeviceNet
1787-6.5.3
DeviceNet Media
1485-CG001A-EN-P
Cable Connection Systems – for I/O connectors
889-CG001A-US-P
DeviceLogix User Manual
ACIG-UM001A-EN-P
800F DeviceNet Push Button Stations
General Specifications
Degree of Protection
(Operator Dependant)
IP66, NEMA Type 4/4X/13
Operating Ambient
Temperature
-25°C to 55°C (-13° F to +131° F) Operating temperatures below
Storage Ambient
Temperature
-40°C to 70°C (-40°F to 158°F)
Vibration
10 – 2000Hz, 1.52mm displacement (peak to peak) max./2.5G max.
Shock
½ cycle sine wave for 11milliseconds at 15G
Relative Humidity
0 to 95%
Certifications
UL, CSA, and CE compliant for all applicable directives. CE
directives include EN61000-6-2, EN61000-6-4
This product is intended for use in an industrial environment.
DeviceNet
Specifications
Max
Min
DeviceNet Voltage
25V DC – Class II Power Supply Required
11V DC
DeviceNet Current
@ 24VDC *
930mA max load (1 sensor @ 50mA, 2
outputs @300mA)
150mA no load
operation
External Input
Specifications
Max
Min
Sensor Source
Current/Voltage
50mA / 26.5V
– /
23V
External
Inputs per Station
4: Dry contact or sinking/sourcing devices
0
External Output
Specifications
Max
Min
Output Auxiliary
Voltage
26.5V
23.5V
On-state Voltage
Drop
0.5V
–
On-state current *
300mA per output, 500mA per station (total)
–
Off-state leakage
0.05mA
–
External E-Stop
Specifications
Max
Min
Voltage
250V
–
On-State Current
13mA nominal
Switching current
per contact block
3A
–
* Please refer to the following thermal derating curves for external outputs at low
DeviceNet voltages
0°C are based on the absence of freezing moisture and liquids.
Default I/O Bytes – Following are the out-of-box settings for the I/O word
format. The default I/O connection size is 2 Input Bytes and 1 Output Byte.
The size and meaning of the data can be changed by the user. For more
information, please refer to the User Manual – 800-UM002A-EN-P.
I/O
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Input
Byte 0
Input 7 Input 6 Input 5 Input 4 Input 3 Input 2 Input 1 Input 0
Input
Byte 1
N/A
N/A
N/A
Out 3
Short
Circuit
Out 2
Short
Circuit
Power
Supply
Fault
SSV2
Short
Circuit
SSV1
Short
Circuit
Output
Byte 0
N/A
N/A
N/A
N/A
Out 3
Out 2
Out 1
Out 0
DeviceLogix is a trademark of Rockwell Automation.
Minimum DeviceNet Voltage vs. Temperature
for Maximum External Load
10
11
12
13
14
15
16
17
18
-25 -20 -15 -10 -5 0
5 10 15 20 25 30 35 40 45 50 55
Temperature (C)
D
ev
ic
eN
et
V
ol
ta
ge
(V
)
Maximum External Load vs. Temperature
for Minimum DeviceNet Voltage
0
100
200
300
400
500
600
-25 -20 -15 -10 -5 0
5 10 15 20 25 30 35 40 45 50 55
Temperature (C)
To
ta
l E
xt
er
na
l L
oa
d
(m
A
)