Rockwell Automation 20-XCOMM-IO-OPT1 I/O Board Option 20-XCOMM-IO-OPT1 User Manual
Installation instructions, I/o board option 20-xcomm-io-opt1
I/O Board Option 20-XCOMM-IO-OPT1
Installation Instructions
These Installation Instructions are provided with the I/O
Board option for use with the External Comms Kit 20-
XCOMM-DC-BASE. This document explains how to install
the I/O board into the kit, and provides board specifications
and I/O wiring details.
This I/O Board option provides additional I/O (6 DC inputs
and 2 relay outputs) for the network — not the drive.
Compatability
To use the I/O board, the installed communication adapter
must be the following hardware series and firmware revision
release or higher:
Important: Even though the 20-COMM-B BACnet MS/TP
and 20-COMM-M Modbus/TCP adapters can
be operated in a 20-XCOMM-DC-BASE
Comms Kit, the adapter’s limitations cannot
support the I/O board option.
Installing the I/O Board
1. Remove J1, 12-position Terminal Block Connector.
2. Insert the black bezel into the base of the light pipe
3. Carefully align the light pipe assembly over the 8 LED
indicators and snap it into the slots on the board.
4. Set JMP 1 Fault Action Jumper for either Fault
Configurable (FLT position, pins 1-2) or Hold Last State
(HLS position, pins 2-3). See
for details.
5. Carefully align the I/O board socket onto the mating plug
of the Comm Kit’s power supply board while placing the
I/O board onto the three standoffs.
6. Fasten the I/O board to the standoffs using the three
screws supplied with the I/O board.
7. Reinstall J1, 12-position Terminal Block Connector.
8. Fasten the enclosure cover onto the Comm Kit’s base
using the two screws in the cover.
Figure 1 Installing the Optional I/O Board
I/O Wiring
Refer to
for I/O function descriptions for each
terminal point on the I/O connector.
Figure 2 I/O Connector Function Descriptions
Communication Adapter
Required
Hardware
(or higher)
Required
Firmware
(or higher)
20-COMM-E EtherNet/IP
Series B
v3.001
20-COMM-C ControlNet (coax)
Series B
v2.001
20-COMM-Q ControlNet (fiber)
Series A
v2.001
20-COMM-D DeviceNet
Series B
v2.001
JMP1 Fault Action Jumper
HLS (Hold
Last State)
Position
FLT (Fault)
Configurable
Position
1
JMP1 FLT
JMP1 FLT
HLS
HLS
2
3
1
2
3
Light Pipe
Black Bezel
I/O Board
J1
Power Supply
Board
Mating Plug
I/O Board Socket
O2 - NO
O2 - COM
O1 - NC
O1 - NO
O1 - COM
IN1
IN2
IN3
IN4
IN5
IN6
INPUT COM
OUT2
OUT1
3 4
5
6
2
1
9 10 11 12
8
7