Specifications, Fuses and Circuit Breakers
Drive Ratings
Catalog
Number
(1)
Output Ratings Input Ratings
Branch Circuit Protection
Power
Dissipation
kW (HP)
Amps
Voltage
Range kVA Amps Fuses
140M Motor
Protectors
(3)
(4)
Contactors
Min.
Enclosure
Volume
(5)
(in.
3
)
IP20 Open
Watts
100 - 120V AC (±10%) – 1-Phase Input, 0 - 230V 3-Phase Output
22B-V2P3x104 0.4 (0.5)
2.3
90-132
1.15 9.0
15
140M-C2E-C16 100-C12
1655
40
22B-V5P0x104 0.75 (1.0)
5.0
90-132
2.45 20.3
35
140M-D8E-C20 100-C23
1655
60
22B-V6P0x104 1.1 (1.5)
6.0
90-132
3.0
24.0
40
140M-F8E-C32 100-C37
1655
80
200 - 240V AC (±10%) – 1-Phase
(2)
Input, 0 - 230V 3-Phase Output
22B-A2P3x104 0.4 (0.5)
2.3
180-264 1.15 6.0
10
140M-C2E-B63 100-C09
1655
40
22B-A5P0x104 0.75 (1.0)
5.0
180-264 2.45 12.0
20
140M-C2E-C16 100-C12
1655
60
22B-A8P0x104 1.5 (2.0)
8.0
180-264 4.0
18.0
30
140M-D8E-C20 100-C23
1655
85
22B-A012x104 2.2 (3.0)
12.0
180-264 5.5
25.0
40
140M-F8E-C32 100-C37
2069
125
200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output
22B-B2P3x104 0.4 (0.5)
2.3
180-264 1.15 2.5
6
140M-C2E-B40 100-C07
1655
40
22B-B5P0x104 0.75 (1.0)
5.0
180-264 2.45 5.7
10
140M-C2E-C10 100-C09
1655
60
22B-B8P0x104 1.5 (2.0)
8.0
180-264 4.0
9.5
15
140M-C2E-C16 100-C12
1655
85
22B-B012x104 2.2 (3.0)
12.0
180-264 5.5
15.5
25
140M-C2E-C16 100-C23
1655
125
22B-B017x104 3.7 (5.0)
17.5
180-264 8.6
21.0
30
140M-F8E-C25 100-C23
1655
180
22B-B024x104 5.5 (7.5)
24.0
180-264 11.8 26.1
40
140M-F8E-C32 100-C37
2069
235
22B-B033x104 7.5 (10.0)
33.0
180-264 16.3 34.6
60
140M-G8E-C45 100-C60
2069
305
380 - 480V AC (±10%) – 3-Phase
Input, 0 - 460V 3-Phase Output
22B-D1P4x104 0.4 (0.5)
1.4
342-528 1.4
1.8
3
140M-C2E-B25 100-C07
1655
35
22B-D2P3x104 0.75 (1.0)
2.3
342-528 2.3
3.2
6
140M-C2E-B40 100-C07
1655
50
22B-D4P0x104 1.5 (2.0)
4.0
342-528 4.0
5.7
10
140M-C2E-B63 100-C09
1655
70
22B-D6P0x104 2.2 (3.0)
6.0
342-528 5.9
7.5
15
140M-C2E-C10 100-C09
1655
100
22B-D010x104 4.0 (5.0)
10.5
342-528 10.3 13.0
20
140M-C2E-C16 100-C23
1655
160
22B-D012x104 5.5 (7.5)
12.0
342-528 11.8 14.2
25
140M-D8E-C20 100-C23
2069
175
22B-D017x104 7.5 (10.0)
17.0
342-528 16.8 18.4
30
140M-D8E-C20 100-C23
2069
210
22B-D024x104 11.0 (15.0) 24.0
342-528 23.4 26.0
50
140M-F8E-C32 100-C43
2069
300
460 - 600V AC (±10%) – 3-Phase
Input, 0 - 575V 3-Phase Output
22B-E1P7x104 0.75 (1.0)
1.7
414-660 2.1
2.3
6
140M-C2E-B25 100-C09
1655
50
22B-E3P0x104 1.5 (2.0)
3.0
414-660 3.65 3.8
6
140M-C2E-B40 100-C09
1655
70
22B-E4P2x104 2.2 (3.0)
4.2
414-660 5.2
5.3
10
140M-D8E-B63 100-C09
1655
100
22B-E6P6x104 4.0 (5.0)
6.6
414-660 8.1
8.3
15
140M-D8E-C10 100-C09
1655
160
22B-E9P9x104 5.5 (7.5)
9.9
414-660 12.1 11.2
20
140M-D8E-C16 100-C16
2069
175
22B-E012x104 7.5 (10.0)
12.2
414-660 14.9 13.7
25
140M-D8E-C16 100-C23
2069
210
22B-E019x104 11.0 (15.0) 19.0
414-660 23.1 24.1
40
140M-F8E-C25 100-C30
2069
300
(1)
In the Catalog Numbers listed “x” represents enclosure type. Specifications are valid for all
enclosure types. IP66, NEMA/UL Type 4X drive ratings are only available as Frame B drives.
(2)
200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix
changes from N104 to N114. Filter option is not available for IP66, NEMA/UL Type 4X rated drives.