Rockwell Automation 42D Series 5000 Blue Line with Analog Output User Manual
Installation instructions—photoswitch, Series 5000 blue line with analog output
![background image](/manuals/577172/1/background.png)
1
Installation Instructions—PHOTOSWITCH
R
Series 5000 Blue Line with Analog Output
Photo Head
Retroreflective
Standard Diffuse
Fixed Focus
Wide Angle
Fiber Optic
Infrared Glass
Fiber Optic
Visible Red Plastic
Catalog Number
42DRU--5400
42DRP--5400
42DRA--5400--FF
42DRF--5400--FF
42DRA--5400--WA
42DRF--5400--WA
42DRA--5400--FO
42DRF--5400--FO
Sensing Distance
4.6m (15ft) total
4.0m (13ft) linear
1.5m (5ft) total
1.2m (4ft) linear
(IR) 127mm (5in) max peak @ 3in
(VR) 101.6mm (4in) max peak @ 2in
(IR) 508mm (20in)
(VR) 177.8mm (7in)
Depends on fiber optic cable
Transmitting LED
Infrared 880nm
Infrared 880nm
(42DRA) Infrared 880nm (42DRF) Visible Red 660nm
Infrared 880nm
Visible Red 660nm
Indicators
Red: Setpoint A; Green: Setpoint B
Field of View
3_
3_
—
—
Depends on fiber optic cable selected
Sensitivity Adjustment
Yes
Operating Temperature
--40_C to +65_C (--40_F to +150_F)
Relative Humidity
90% maximum
Housing/Lens Material
Valox
/Acrylic
Valox
/Acrylic
Cover Gasket Material
Nitrile
Operating Environment
NEMA 3, 4, 12, 13, and IP66 (IEC 529), corrosion resistant, high-impact housing
Approvals
UL listed, CSA certified (except cable style power base), and CE marked for all applicable directives
Protections
Output short-circuit (analog only)
Vibration
10--55 Hz, 1 mm amplitude, Meets or exceeds IEC 947--5--2
Shock
30G, Meets or exceeds IEC 947--5--2
Supply Voltage/Current
22--28V DC/70mA max
Output Type
Analog 1--20mA current or 1--10V DC voltage (selectable negative or positive slope) (2) NPN setpoints (selectable)
Output Load
900 (analog current); 3K minimum (analog voltage); 28V DC, 100mA (setpoints)
Load Current
100mA
Leakage Current
10A max.
Response Time
100ms (time required for analog swing)
Photo Base
Screw Terminal (nickel-plated brass
pressure type terminal #6--32
42DTB--5000
3m Cable (5 conductor flexible PVC
jacketed cable 3m (10ft))
42DCB--5000
Sensing modes may be field configurable by selecting either the 42DRA--5400 or 42DRF--5400 photohead and one of the following lens assemblies: 61--5551 for fixed focus sensing mode, 61--5511 for wide angle diffuse sensing
mode.