Parameter settings, Parameters settings – Rockwell Automation 22A PowerFlex 4 Custom Firmware Instructions - Option DA User Manual
Page 2
P035 [Maximum Freq]
Values
Default 60
Hz
Min/Max:
0/300.0
Hz
Display:
1
Hz
A069 [Internal Freq]
Values
Default 60.0
Hz
Min/Max:
0.0/300.0
Hz
Display:
0.1
Hz
A070 [Preset Freq 0]
A071 [Preset Freq 1]
A072 [Preset Freq 2]
A073 [Preset Freq 3]
Values
A070 Default
A071 Default
A072 Default
A073 Default
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
Min/Max:
0.0/300.0
Hz
Display:
0.1
Hz
P042 [Initial Braking Pressure] – New Parameter
This is the new parameter, which affects the DC braking performance.
Values
Default 1200
Min/Max:
80/2000
Display:
1
Parameters Settings
The following parameters may need to be adjusted for the quick stop application.
P037 [Stop Mode]
Set this parameter to one of the DC braking modes (2, 3, 6, or 7).
Mode 3 is probably the preferred mode, but mode 2 may provide slightly better
performance if there is mechanical inertial or and mechanical backlash. Mode 3
applies braking until the drive stops then releases the brake. If there is still some
external mechanical inertia when the brake is released the drive (system) may coast
for a short distance. Mode 2 applies the brake for the full period of time specified in
parameter 80 acting as a holding brake even after the motor comes to rest. Mode 6
is the same as Mode 2 and Mode 7 is the same as Mode 3 except that Mode 6 and 7
do not permit a simple stop to clear faults if they occur.
PowerFlex 4 Custom Firmware
2