beautypg.com

Rockwell Automation 42JT-D2LAT1_D8LAT1 VisiSight Photoelectric Diffuse Sensors User Manual

With io-link, Sensor user interface led status, General specifications

background image

Installation Instructions

42JT VisiSight™ Photoelectric Diffuse Sensors

with IO-Link

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.

Default Settings:

The factory default settings are configured so that no teaching is
required for a vast majority of the applications.

Sensing Range: Maximum Setting
Output Mode: Light Operate (Output ON when target is
detected)
Output Type: Auto PNP/NPN or IO-Link. In Auto PNP/NPN mode,
the sensor continuously monitors the load connection and
automatically configures the output to PNP or NPN.

Sensor User Interface

LED Status

The table below provides LED status in the RUN mode, during
operation. The sensor is always in RUN mode, except when being
taught.

Auto PNP/NPN Operation

IO-Link Operation

Connection Types

Green

OFF

Power is OFF

ON

Power is ON

Flashing (6 Hz)

Unstable light level (0.5 < margin < 2)

Flashing (1.5 Hz)

Output short circuit protection active

Yellow

OFF

Output de-energized

ON

Output energized

Green

OFF

Power is OFF

Flashing (1 Hz)

Power is ON

Yellow

OFF

Output de-energized

ON

Output energized

Cat. No. Suffix

Description

-A2

2 m cable

-P4

Integral 4-pin pico (M8) QD

-F4

4-pin DC micro (M12) QD on 150 mm (6 in.) pigtail

-Y4

4-pin pico (M8) QD on 150 mm (6 in.) pigtail

Yellow LED

Push button

Green LED

General Specifications

 see Connection Types table
 ECOLAB on P4 and A2 models only.
 UL: -20…+50°C (-4…122°F)
 UL: Class 2 source

Mounting the Sensor

Securely mount the sensor on a firm, stable surface or support.
An application which is subject to excessive vibration or shifting
may cause intermittent operation. For installation convenience,
Rockwell Automation offers a wide range of mounting brackets
(see the Accessories section for more details).

Alignment Indication

For short range applications the visible light beam of the sensor
suffices as alignment aid.

The alignment feature may be used for longer range applications.
Alignment of the sensor is indicated via change in intensity of the
green LED in the Alignment Mode, as follows:

42JT-D2LAT1-

42JT-D8LAT1-

Environmental

Certifications

cULus and CE Marked for all applicable directives

Operating Environment

IP67, IP69K, ECOLAB

Operating Temperature [C (F)]

-20…+60° (-4…+140°)

Storage Temperature [C (F)]

-20…+80° (-4…+179°)

Optical

Light Source

Visible red 660 nm

Class 1 laser 650 nm

Sensing Range

3…800 mm
(0.12…31.5 in.)

1…250 mm
(0.04…9.8 in.)

Adjustments

Push button

Electrical

Voltage

10…30V DC

Current Consumption

30 mA max.

Sensor Protection

Reverse polarity, short circuit, overload
protection

Outputs

Response Time

0.5 ms max.

0.33 ms max.

Output Type

Auto NPN or PNP

Output Function

Selectable light operate or dark operate

Output Current

100 mA max.

Output Leakage Current

10 μA max.

Mechanical

Housing Material

ABS

Lens Material

PMMA

Cover Material

PMMA