Publication PA--9169(A)

September 1992

Calibration of Analog Output

Calibration of the Analog Output is done with a Voltmeter or an

Ammeter. When calibrating the Voltage Output, connect the Voltme-

ter between Terminal 2 (+) and the negative power supply Terminal 1

(--). Select the Voltmeter Scale for 10VDC. When calibrating the Cur-

rent Output, install the Ammeter between Terminal 2 (--) and the posi-

tive power supply Terminal (+), or the positive of a separate power

supply when used. Select the Ammeter scale for 20mA (DC).

1. With Selector Switches 1 and 2, select Analog Current or Voltage

Output.

2. With Selector Switches 3 and 4, select Diffuse or Retroreflective

operation.

Retroreflective Operation

1. Set retroreflective target at 2 (.61m). Adjust the Analog Output

Calibration pot. for 10VDC or 20mA (2%).

2. Set the retroreflective target at the desired range. 15 (4.57m)

maximum, 5 (1.52m) minimum. Adjust the Sensing Range Ad-

justment pot. for 1VDC or 1mA (10%).

3. Bring the retroreflective target back to 2 (.61m). Re-adjust the

Analog Output Calibration pot. for 10VDC or 20mA (2%) if

necessary.

4. Place the retroreflective target at the desired range. Re-adjust the

Sensing Range Adjustment pot. for 1VDC or 1mA (10%) if

necessary.

The Analog Output is now calibrated for Retroreflective operation.

Diffuse Operation

1. Place the object to be detected at 1 (.3m). Adjust the Analog

Output Calibration pot. for 10VDC or 20mA (2%).

2. Set the object to be detected back to the desired range, 5 (1.52m)

maximum or 3 (.91m) minimum. Adjust the Sensing Range Ad-

justment pot. for 1VDC or 1mA (10%).

3. Bring the object to be detected at 1 (.3m). Re-adjust the Analog

Output Calibration pot. for 10VDC or 20mA (2%) if necessary.

4. Place the object to be detected at the desired range. Re-adjust the

Sensing Range Adjustment pot. for 1VDC or 1mA (10%) if

necessary.

The Analog Output is now calibrated for Diffuse operation.
Calibration of Setpoint Outputs

1. Place the retroreflective target at the distance where the Setpoint

Output A is to come on.

2. Adjust the Setpoint pot. A to turn on Output A at this point. (Red

LED turns on.)

3. Place the retroreflective target at the distance where the Setpoint

Output B is to come on.

4. Adjust the Setpoint B to turn on Output B at this point. (Green

LED turns on.)

Note: Be aware that in the retroreflective mode, when setting the

range beyond 11 (3.35m), white paper response may occur

between 1 (2.54cm) and 1 (.3m).

This completes the calibration of Setpoint Outputs.

INSTALLATION

The control must be securely mounted on a firm, stable surface or support. A mounting

which is subject to excessive vibration or shifting may cause intermittent operation.

OUTLINE DIMENSIONS

1 3/4

DIA.

11/32

(8.73)

61/64

(24.2)

15/32

(11.9)

39/64

(15.4)

2 7/8

(73.0)

3/4

(19.0)

.325

(8.26)

2 21/32

(67.5)

2

(50.8)

.280

(7.10)

.325

(8.26)

2 21/32

(67.5)

.280

(7.10)

11/32

(8.73)

61/64

(24.2)

15/32

(11.9)

39/64

(15.4)

1 11/16

(42.9)

3/4

(19.0)

MATERIAL

#11 GA CRS

2 57/64

(73.42)

Control with Cable Base

4 1/4

(106.5)

5 25/64

(136.9)

2

(50.8)

5 7/16

(138.1)

4.0

(101.6)

CLEARANCE FOR

#1/4--20 HDW

GENERAL PURPOSE

MOUNTING

60-1785

11/32

(8.73)

61/64

(24.2)

15/32

(11.9)

39/64

(15.4)

2 27/32

(72.3)

11/32

(8.73)

61/64

(24.2)

15/32

(11.9)

39/64

(15.4)

Control with

Cable Base

Control with

Terminal Base

1

(25.4)

1 53/64

(46.43)

4 7/64

(104.4)

CLEARANCE

FOR #10-32 HDW

2 1/2

(63.5)

1 1/2

(38.1)

1 1/2

(38.1)

2

5/32

(54.7)

1/4 (6.3)

1 14/32

(61.9)

21/64

(8.3)

1

(25.4)

5 24/32

(146.4)

4 11/32

(110.3)

2 1/2

(63.5)

1 1/4

(31.7)

#10-32

THREAD

2 HOLES

59/64

(23.4)

1/4

(6.3)

CLEARANCE

FOR #10-32 HDW

2 1/2

(63.5)

1 1/2

(38.1)

1/4 (6.3)

1 14/32

(61.9)

21/64

(8.3)

2 5/32

(54.7)

Control with Terminal Base

HEAVY

DUTY MTG.

60-1748

WIRING

All external wiring should conform to the National Electric Code and applicable local codes. See wiring diagrams for external connectins.

+

2

--

FLOATING

SHIELD

TERMINAL

BASE

CABLE BASE

(+) 22--28

VDC

GRAY

BLACK

ANALOG VOLTAGE OUTPUT CONNECTIONS

RED

(--)

VOLTAGE

SENSOR

R = 3k Ohm

MIN

+

2

--

FLOATING

SHIELD

TERMINAL

BASE

(+) 22--28

VDC

GRAY

BLACK

RED

(--)

CURRENT

SENSOR

SUPPLY VOLTAGE -- 10V

20MA

(+) 40 VDC

MAX

RMAX =

ANALOG CURRENT OUTPUT CONNECTIONS

CABLE BASE

+

3

1

--

LOAD

FLOATING

SHIELD

TERMINAL

BASE

CABLE BASE

( + ) 22--28

VDC

ORANGE

BLUE

BLACK (--)

NPN SET POINT OUTPUT CONNECTIONS

RED

( + ) 10--30

VDC

( + ) 10--30

VDC

(--)

100mA MAX

100mA MAX

LOAD