Powerflex 4/40 custom firmware – Rockwell Automation 22B PowerFlex 4/40 Custom FW, DB-Modbus Enhancement User Manual
Page 2

A.1 PLC Read Registers - Output from Drive
Register (ID)
Name
Type
Range
2048
Logic Status Word
Binary
Binary defined (A.2)
2049
Reserved
Integer 16 bit
2050
Reserved
Integer 16 bit
2051
Output Frequency (Feedback)
Integer 16 bit
0..240.00 Hz
2052
Output Speed (Feedback)
Integer 16 bit
0..10000 RPM
2053
Output Current
Integer 16 bit
0..99.9 A
2054
Heat Sink Temperature
Integer 16 bit
0..120°C
2055
Motor Power
Integer 16 bit
0..99.99kW
2056
Output Voltage
Integer 16 bit
0..999.9 V
2057
Energy
Integer 16 bit
0..65535kWh
2058
Drive Error (same as D007)
Integer 16 bit
0..122
Note: All values are without sign. The Modbus values have there decimal point adjusted as
defined in the table and not as defined in the standard instruction manual.
A.2 Definition for the Logic Status Word
Bit 15 – 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Not used
Running at
Zero Speed
At Freq
Alarm
Faulted Running
+
Backward
Running
Ready
Detailed bit description:
Running at Zero Speed
Bit = 1 when speed is below 2% of max frequency
At Freq
Bit = 1 when output frequency reached frequency command.
Alarm
Bit = 1 when alarm is active
Faulted
Bit = 1 when drive has tripped on fault.
Running + Backward
Bit = 1 when running backwards
Running
Bit = 1 when running
Ready
Bit = 1 when ready and accepting frequency commands.
A.3 PLC Write Registers - Input to Drive
Register (ID)
Name
Type
Range
2000
Logic Control Word
Binary 16 bit Binary defined (A.4)
2001
Reserved
Binary 16 bit
2002
Frequency Command relative to P035
Integer 16 bit
0..100.00% Fmax
2003
Reserved for customer, not used in the drive
Integer 16 bit
2004
Reserved for customer, not used in the drive
Integer 16 bit
2005
Reserved for customer, not used in the drive
Integer 16 bit
2006
Reserved for customer, not used in the drive
Integer 16 bit
The first register 2000 is used for the “Logic Control Word” and the register 2002 for the
“Frequency (Speed) Command”. The following up 4 registers from 2003 to 2006 are especially
reserved for the customer and are not used in the drives but external.
PowerFlex 4/40 Custom Firmware