INSTALLATION INSTRUCTIONS
PHOTOSWITCH
R
SOLID STATE PLUG IN LOGIC OUTPUTS
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. REPLACEMENT PARTS FOR BASES MANUFACTURED AND SOLD BEFORE 1991.
BULLETIN NUMBER
TYPE
VOLTAGE SUPPLY
CURRENT RATING
RESPONSE TIME
63--64
or
63--66
DC Voltage
Output Adapter
24 VDC
30 mA
Depends upon
Control Used
12 VDC
15 mA
63--65
or
63--67
Open Collector
Logic Output
24 VDC
250 mA
15 VDC
150 mA
12 VDC
125 mA
63- 64 or 63- 66
SPECIFICATIONS
No Load
20 VDC
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Resistance
Not less than 550 Ohms
. . . . . . . . . . . . . . . . . . . .
Ambient Temperature Range
--20°F to 135°F (--28°C to 57°C)
. .
Relative Humidity
95%
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Note: 63--66 and 63--67 Outputs supersede the 63--64 and 63--65 Out-
puts respectively. The new plug-in Outputs are electrically and
physically interchangeable with the old, but with the following
minor exceptions.
1.
The plastic cover on the 63--66 and 63--67 have curved domes
to match the curved spring retainers supplied on all Control
Bases with date code 8000 and higher.
2.
For Series 60--1400 and 60--1600 Control Bases manufactured
and installed prior to January 1980, which included the flat-top
spring retainer, order the 63--66 plus a 63--71 flat--top Adapter
for compatible Control Base mounting.
63- 65 or 63- 67
SPECIFICATIONS
Open Collector Rating as Current Sink
250mA for Vce = .25
. .
Ambient Temperature Range
--20°F to 135°F (--28°C to 57°C)
. .
Relative Humidity
95%
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reverse Voltage Protection
Shunt Diode
. . . . . . . . . . . . . . . . . . . .
3.
When these Logic Adapters are used with Model 4003 Versions
of Type 42RL Controls, only DC input power should be ap-
plied. The user must also be certain to add a jumper between
control terminals L2 and 2C. This ties the negative power sup-
ply line terminal to the negative of the output circuit. In placing
this jumper and in connecting the power supply leads, the cor-
rect polarity must be observed to avoid internal damage.