Replacing the Power Supply
Assembly

1. Verify that the metal standoff is fastened securely to the Power Interface

Assembly. Torque = 1.4 to 1.8 N-m (13 to 16 in/lb).

2. Install (or re-use) the three plastic spacers (p/n 179773).

3. Place the insulation sheet onto the plastic spacers over the Power

Interface Assembly. Verify that the warning label is at the bottom of the
sheet when installed.

4. Press the Power Supply Assembly (p/n 193087-A02) onto the plastic

spacers until fastened.

5. Fasten (and ground) the Power Supply Assembly to the Power Interface

Assembly using the PHMS screw (p/n 419062-1PGF). Torque = 1.4 to
1.8 N-m (13 to 16 in/lb).

6. Connect the wiring harnesses between the assemblies.