Programming, General specifications dimensions, Dimensions are in millimeters and (inches) – Rockwell Automation 20D PowerFlex 700S Auxiliary Control Power Supply User Manual
Page 3

Programming
Set parameter 153 [Control Options], Bit 17 Aux Pwr Sply to “1” to enable operation.
General Specifications
Dimensions
– Dimensions are in millimeters and (inches)
Category
Specification
Electrical
Input:
(1)
(1)The PowerFlex 700S Auxiliary Control Power Supply keeps the drive’s control power operating when drive power is removed. For 575/600
volt drives, where the Auxiliary Control Power Supply is required to start a drive power supply, the input voltage to the Auxiliary Control Power
Supply must exceed 24 volts at the input terminals to ensure the drive power supply will start.
24 Volts +/-10% Isolated, 5 Amps Maximum (Full Load Current)
Output:
300 Volts, 100 Watts Maximum, 0.33 Amps Maximum (Full Load Current)
Fusing:
7.5 Amp ATO Mini Fuse
Grounding:
Case is grounded through GND terminal on Input Terminal Block. Mount to grounded surface or ground via Grounding
Stud. Use 0.2 mm
2
(24 AWG) wire for grounding stud connection.
Power Dissipation:
20 Watts
Environment
Maximum Surrounding
Air Temperature:
0-50 degrees C (32 to 122 degrees F)
Storage Temperature:
–40 to 85 degrees C (–40 to 185 degrees F)
Enclosure:
For UL installations, mount in a NEMA Type 1 enclosure
Relative Humidity:
5 to 95% non-condensing
Shock:
30G peak for 11ms duration (–/+1.0 ms)
Vibration:
0.381 mm (0.015 in.) displacement, 2.5G peak
Other
LED Indicator:
Illuminated LED indicates unit is powered. Darkened LED indicates unit is fully discharged.
Use:
Unit is designed to provide control power to one drive only.
Compatible Drives:
PowerFlex 700S Drives: All voltage classes.