beautypg.com

Vicor Westcor PFC Mini Power Factor Corrected AC-DC Switcher User Manual

Page 23

background image

UG:115

vicorpower.com

Applications Engineering: 800 927.9474

Page 23

Maxi, Mini, Micro Series Modules (Maxi and Mini Modules Only)

Parameter

MIN

TYP

MAX

UNITS

Notes

Setpoint Accuracy

[d]

Load Regulation

±0.5
±0.1

±1

% of Vnom
% of Vnom

See module design guide
for exact specifications

Temperature Regulation

0.002

0.005

%/°C

-20°C to 100°C

Long Term Drift
Output Ripple & Noise:
≤10 V out
>10 V out

100

1.0

mV

% Vout

20 MHz bandwidth
20 MHz bandwidth

Voltage Trim Range
Maxi/Mini Slots

10-110

% Vout

Preload may be required

Total Remote Sense
Compensation

0.5

Volts

Autosense.
See Pages 8 & 14

OVP Set Point

112

135

% Vout

Recycle Power

Current Limit

115

135

% of I max

Auto Recovery

Overtemperature Limiting

100

115

MMM OTL is non-latching

[d]

For special, adjustable voltages and 48 Vdc outputs, maximum setpoint accuracy is 2% of Vnom.

Note: See individual module data sheets for specific module specifications.