ConverterPAC Functional Description (Cont.)
FlexPAC
The FlexPAC output assembly consists of from 2 to 4 discrete outputs that convert the
high output bus to the desired output voltage. Each FlexPAC output can be manually
trimmed from 2V to 25V and supports up to 5 amps with a maximum output powerof
50W per output. All outputs maintain less than 50mV noise over the entire output
range. All outputs support local sense only. For electrical trim options and specific
output sequencing contact the factory
List of ConverterPACs used in the 3 Phase/4kW MegaPACs and their features
ConverterPAC
OVP
OCP
OTL
RS/AS*
LS/AS*
PG
TrimPot
ModuPAC
Std
Std
Std
AS*
AS*
Opt
Opt
JuniorPAC
N/A
Std
N/A
AS*
AS*
Opt
Opt
DualPAC
N/A
Std
N/A
AS*
AS*
N/A
Opt
RAMPAC
N/A
Std
N/A
AS*
AS*
Opt
Opt
BatPAC
N/A
Std
N/A
N/A
N/A
N/A
Std
UniPAC**
Std
Std
N/A
AS*
AS*
Opt
Opt
* See page 13 and 17 for more information on Autosense.
**
Currently, the UniPAC (XU) can only be used in the 4kW MegaPAC.
OVP
Overvoltage Protection (latching)
OCP
Overcurrent Protection (auto-recovery)
OTL
Overtemperature Limiting (latching)
RS
Remote Sense
PG
Power Good (DC OK TTL Signal)
LS
Local Sense
AS Autosense
Note: All ConverterPACs mentioned above can be paralleled EXCEPT the DualPAC,
JuniorPAC and RamPAC.
M-1 STATUS
M-1 VOLTAGE ADJUSTMENT
M-4 STATUS
M-3 STATUS
M-2 VOLTAGE ADJUSTMENT
M-2 STATUS
M-4 VOLTAGE ADJUSTMENT
M-3 VOLTAGE ADJUSTMENT
CONNECTOR
J1
FlexPAC