Aerocross sensor - calibration curves – Titus QCV IOM User Manual

Page 2

background image

QCV-IOM-1.0 2-28-13

Unit

Damper

Size

SQ FT

CFM

FPM Quantity Size

A

0.174

320

1837

1

4/5

B

0.250

477

1908

1

4/5

C

0.333

629

1890

1

4/5

D

0.555

1047

1886

1

8

E

0.778

1539

1978

1

8

F

0.750

1472

1962

2

4/5

G

0.833

1676

2012

1

10

H

1.250

2619

2095

2

10

J

1.500

3036

2024

1

12

K

1.944

4385

2256

1

16

L

2.500

5582

2233

2

12

M

2.444

5847

2392

1

16

N

3.000

7413

2471

1

16

P

4.167

11224

2693

2

16

R

5.555

16496

2970

2

16

K-Factor

Sensor

AeroCross Sensor - Calibration Curves

Inlet Sensor Applications (For QCV's)

P = Differential Pressure On AeroCross,

IN WG

K = Flow Required To Produce A 1.0 IN WG

Differential Pressure On AeroCross,

CFM

CFM = K P

P = CFM

K

2

Equations: