I N S T A L L A T I O N & O P E R A T I O N M A N U A L
FFD, FFDR, FFDRA Models
Fan Filter Unit IOM
Installation & Operation
Cleaning the Pre-filter (foam)
Tools Required: None.
Note:
To keep the filter in top operating condition, washing
the foam prefilter is recommended every three to six months.
Step 1.
To gain access to the prefilter, remove the ceiling
panel next to the unit, if applicable.
Step 2.
Switch the ON-OFF switch to the off position.
Step 3.
Remove the 16”x23” prefilter from the snap-in frame. (See figure below)
Step 4.
Clean the prefilter by hand washing in water with a mild detergent or by using a vacuum cleaner . Allow prefilter to
dry completely before replacing.
Step 5.
Reassemble by reversing the above steps.
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
ANY SERVICE
PREFILTER SURFACE ON TOP SIDE
SUPPORT SCREEN ON BOTTOM SIDE
ON/OFF SWITCH
7
- ACC1 Small System Console (12 pages)
- Alpha BAC-8001/BAC-8201 Cooling Only (21 pages)
- Alpha BAC-8007/BAC-8207 Dual Duct (26 pages)
- Alpha Commissioning Guide (5 pages)
- Analog T3SQ-1 IOM (6 pages)
- Atlas Operating Room Ceiling System (AORCS) (10 pages)
- Displacment Ventilation (22 pages)
- Dual Duct Terminal IOM (2 pages)
- ECM Motor Infrared Controls (2 pages)
- Electric Heat IOM (10 pages)
- Fan Powered Term. IOM (9 pages)
- FFDE/FFDER/FFDERA (27 pages)
- Fire Rated IOM (4 pages)
- FlowBar IOM (16 pages)
- HAB Horizontal Air Handler Belt Drive (11 pages)
- HEPAlert IOM for RadiaTec Diffusers (7 pages)
- HEPAlert IOM for TLF Diffusers (7 pages)
- Horizontal Basic IOM (6 pages)
- Horizontal High Output IOM (6 pages)
- LSC IOM (27 pages)
- Lynergy (7 pages)
- MAB IOM (9 pages)
- Mixing Box Controls IOM (15 pages)
- ML Border 22 (2 pages)
- ML IOM (8 pages)
- Pneumatic Controls for Dual Duct Terminals IOM (9 pages)
- Pneumatic Controls IOM (10 pages)
- QCV IOM (2 pages)
- RAB IOM (12 pages)
- RadiaTec IOM (9 pages)
- Sensor STE-8001 and STE-8201 (34 pages)
- Single Duct Terminal IOM (2 pages)
- SteriTec/LineaTec IOM (2 pages)
- T3SQ-2 Commissioning Guide (4 pages)
- T3SQ-2 IOM (8 pages)
- T3SQ-2 QuickStart Manual (4 pages)
- T3SQ-2 Thermostat Operating Manual (6 pages)
- TAF-L Perimeter System IOM (10 pages)
- TAO IOM (3 pages)
- TBD/TBDR-FR IOM (2 pages)
- Thermal T3SQ-4, IOM (2 pages)
- TMR / TMRA IOM (4 pages)
- UnderFloor Products IOM (20 pages)
- Universal Control Card (7 pages)