Titus Electric Heat IOM User Manual
Page 9
On the fan powered terminals, the elements rack is located at the discharge end of the terminal under a metal heater
rack cover held with screws. On the single duct terminals, the element rack is located inside the control enclosure on
the side of the terminal.
1. Turn power off to the terminal unit before servicing.
2. Locate element rack header plate.
3. Before removing wires from the element rack header plate, mark the wires and where they are connected, to insure
they are reconnected correctly on the new element rack.
4. Remove the wires and screws holding the header plate in the coil housing.
5. Insert the new element rack into the coil housing and replace the screws to secure the element rack.
6. Replace wires in the same locations as removed from old element rack.
7. Replace enclosure metal cover or door before turning on power to the electric coil.
Electric Coil Elements
Element Wire Nuts
Heater Rack Replacement
EHeat-IOM-9.0
6-1-01
Flanges mount to discharge of
terminal unit.
Fan powered terminal heater is shown below.
Fan Box Heater
Rack Cover
Heater Rack Header Plate