Page 3

background image

This will enter the SETUP menu step 1, pressing the

key a second time advances to step 2. Each press of the

key advances the menu item. No values are saved or changed

by using the

key. The key is used to make

changes to program variables by scrolling through the available

options. When a value is changed, use the key to save it

to memory and advance to the next menu item.

Press and release the key to enter the SETUP

menu.

1. Out High

The default CO2 range is 0-2000 ppm. The

span can be changed from 1000 to 7500 ppm in

increments of 2000 ppm 500. Use the

key to change the value and to save.

The factory default is 2000 ppm.

2. Altitude

The default is 0 feet. Change by using the

key from 0 to 5000 feet in 500 ft

increments. Change 0 Ft for CO2 local altitude

correction and press to save a change.

3. Auto Cal

Automatic Cal Mode default is ON to correct

CO2 sensor drift to better than ± 10 ppm per

year. Change ON with the key and

save using . ON is recommended for

applications where the CO2 level will be close

to normal (400 ppm) at least once per day. If a

building is occupied 24 hours and the CO2 level

is fairly constant then this should be set to OFF.

4. Output

Use the key to toggle the output OFF

(normal operation), MIN (minimum output) or

MAX Test OFF (maximum output) for testing

purposes. Press either or

to

set it back to OFF and advance to the next item.

5. Calibrat

This item is used for 1000 ppm gas calibration

and is explained in the Calibration section.

1000 PPM

6. BackLite

Use the key to enable or disable the

LCD backlight. When enabled the backlight is

always on, Enable when disabled it never lights.

Press the key to save the setting. The

factory default is Enable.

7. Restore

Press the key to restore all factory

defaults and calibration to original factory

settings.

8. Menu

Press to exit the menu and return to

normal operation or

to repeat the

menu.

General Specifications
Power Supply . . . . . . . . . . . . 20 – 28 Vac/dc (non-isolated half-

wave rectified)

Consumption . . . . . . . . . . . . 100 mA max @ 24 Vdc, 185 mA max

@ 24 Vac (with all options)

Output Signals . . . . . . . . . . . 4-20 mA active (sourcing), 0-5 Vdc

or 0-10 Vdc (field selectable)

Output Drive Capability . . . 550 ohms maximum for current out-

put, 10 Kohm min for voltage output

Output Resolution . . . . . . . . 10 bit PWM
Protection Circuitry . . . . . . . Reverse voltage protected, overvolt-

age protected

Operating Conditions . . . . . 0-50 °C (32-122 °F), 0-95 %RH

non-condensing

Wiring Connections . . . . . . Screw terminal block (14 to 22 AWG)
Sensor Coverage Area . . . . . 100 m2 (1000 ft2) typical
Enclosure . . . . . . . . . . . . . . . Wall mount enclosure, 3.3”w x 4.7”h

x 1.15”d (84 x 119 x 29 mm)

CO2 Signal
Measurement Type . . . . . . . Non-Dispersive Infrared (NDIR),

diffusion sampling

Measurement Range . . . . . . 0-2000 ppm standard, programmable

up to 7500 ppm

Standard Accuracy . . . . . . . . ± 75 ppm @ 1000 ppm @ 22 °C (72

°F) compared to certified calibration

gas

Temperature Dependence . . 0.2 %FS per °C
Stability . . . . . . . . . . . . . . . . . < 2 %FS over life of sensor (15 year

typical)

Pressure Dependence . . . . . . 0.13 % of reading per mm Hg
Altitude Correction . . . . . . . Programmable from 0-5000 ft via

keypad

Response Time . . . . . . . . . . . < 2 minutes for 90 % step change

typical

Warm-up Time . . . . . . . . . . . < 2 minutes
LCD Display
Resolution . . . . . . . . . . . . . . . 1 ppm CO2
Size . . . . . . . . . . . . . . . . . . . . . 1.4” w x 0.6” h (35 x 15 mm) alpha-

numeric 2 line x 8 characters

Backlight . . . . . . . . . . . . . . . . Enable or disable via keypad