beautypg.com

Sensaphone fgd-0007 Infrared MotIon detectIon SenSor User Manual

Sensaphone, Remote monitoring solutions

background image

SENSAPHONE

®

REMOTE MONITORING SOLUTIONS

Infrared MotIon detectIon SenSor • fGd-0007

InstallatIon InstructIons v.3.3

The Infrared Motion Detection Sensor is used to monitor the movement of warm bodies in a specific area. The range is a

maximum of 40 feet directly ahead of, and approximately 20 feet to either side of, the detector at 40 feet distance

(Figure 6). If motion is detected, the sensor will cause a dial-out to occur.

InstallatIon

1. Remove front cover from sensor by placing a flat head

screwdriver in slot located on side of sensor, then

rotate the screwdriver.(Figure 1)

Figure 1: Removing the front cover

Warning: Do not face sensor toward the sun with the

cover off. This will damage the sensor.

2. Remove mounting screws from the holes in the PC

board.

3. Carefully remove the board from the pegs before

attempting to screw the back plate to the wall.

4. Use a small screwdriver to punch out the cable-entry

knock-out (indented circle) in the back cover of the

Infrared Motion Detection Sensor.

Cable Entry

Knockout

Screw Mounting Holes

Figure 2: Cable entry knockout

5. Mounting the back cover to the wall, using the accom-

panying screws and the two knock-out slots for them

in the back cover. The sensor must be mounted with

the long dimension parallel to the floor and ceil-

ing, with the sensor’s window to the left, not up.

The detector can be mounted in either a surface

wall mount position (Figure 3) or in a corner mount

position (Figure 4). Recommended (most effective)

mounting height is 4.5 feet.

WALL

Mounting Screws

Figure 3: Surface mounting the Sensor

WALL

W

ALL

Mounting Screw

Mounting Scre

w

Figure 4: Corner Mounting the Sensor

6. Run two wires through the cable knockout hole and

connect them to the small terminal block (Output) on

the side of the on the infrared circuit board opposite

the reflector unit. (See Figure 5.)
Note: The sensor wiring is not polarity sensitive. It

does not matter which wire goes to which screw ter-

minal.