4. Slip the protective cover into position over the
screw terminals and tighten mounting screws.
5. Run the wires to the Sensaphone and attach them
to the screw terminals of an available input.
PROGRAMMING FOR MODELS
400/800/1400/1800/2800
1. Close the door or window.
2. Set input normality by pressing SET CONFIGURE.
3. Test the sensor by opening the door or window.
A verbal alert message should occur.
PROGRAMMING FOR ExPRESS II/2000/
ScADA 3000, WEB600, cELL682, SAT4D
1. Close the door or window.
2. Set input normality to Normally Closed via the
Inputs menu.
3. Test the sensor by opening the door or window.
A verbal alert message should occur.
MULTIPLE SWITcHES
Several Magnetic Reed Switches may be installed
in series on a single continuous circuit provided all
switches will be normally closed at the same time.
MAGNETIC REED DOOR &
WINDOW SWITCH
FGD-0006 V.1.5
The Magnetic Reed Switch enables your
Sensaphone to detect if any unauthorized entry
or intrusion has occurred. Switches are usually
installed on doors and windows to detect their
opening or closing. The Magnetic Reed Switch can
be used with all Sensaphone models.
INSTALLATION
The switch is usually installed to function in a
normally closed position when the door or window
is closed.
The complete Magnetic Reed Switch assembly
comes in two main parts: a magnet in a plastic
housing, and a switch with screw terminals in
another, separate plastic housing.
1. Fasten the switch to the non-moving frame
surrounding the door or window.
2. Fasten the magnet near the edge of the
moveable sash or door. Position the magnet
housing no more than
1
⁄
8
” from the switch and
tighten mounting screws. Use the spacer bar if
needed for alignment.
3. Attach two separate wires to the two screw
terminals on the switch. The use of 22 gauge
wire is recommended for circuit loops up to
3,000 feet.
LIT-0073