Schwank SEB(U) User Manual
Page 25
SP-MSEB-BX-10A
SEB Manual
RD: JUNE 2004
RL: 10
KH
Page 21
SPARK STOPS WHEN
BURNER LIGHTS
SYSTEM RUNS UNTIL CALL
FOR HEAT ENDS
CALL FOR HEAT ENDS:
SYSTEM SHUTS OFF
YES
YES
YES
YES
NO
NO
NO
NO
SPARK IGNITER MAY BE OUT OF POSITION
CHECK ELECTRICAL CONNECTION FROM IGNI
TION CONTROL PIN #2 TO GAS VALVE.
CHECK FOR 110 VAC ACROSS GAS VALVE IF
OKAY, REPLACE GAS VALVE.
CHECK GROUND WIRE, IGNITER AND HT CABLE.
CHECK THAT BURNER FLAME COVERS ELECTRODE
IF CHECKS ARE OKAY, REPLACE IGNITION CONTROL
NOTE: IF IGNITION CONTROL GOES INTO LOCKOUT, MODE
RESET THE SYSTEM.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS
MAY OCCUR OCCASIONALLY EVEN THOUGH OPERA-
TION IS NORMAL AT THE TIME OF CHECKOUT.
CHECK GROUND WIRE NECTIONS AND CONTINUITY.
IF CHECKS ARE OKAY, REPLACE IGNITION CONTROL
CHECK FOR PROPER TEMPERATURE CONTROLLER
OPERATIONS
REMOVE VALVE LEAD AT IGNITION CONTROL, IF VALVE
CLOSES, RECHECK TEMPERATURE CONTROLLER AND
WIRING, IF NOT, REPLACE GAS CONTROL OPERATOR
TROUBLESHOOTING ENDS
CONTINUED FROM PREVIOUS PAGE
MAIN BURNER LIGHTS