Setting the Communications

You communicate with the meter via a changeable COM1 communication port, or through

a second factory set serial RS-485/RS-422 COM2 port. Depending on what was ordered,

your meter’s COM1 port can be equipped with an RS-232/RS-422/RS-485 serial

interface, with a dial-up modem for communicating through public telephone lines, with

an Ethernet module for communicating through the Internet, or with Profibus DP.
To configure your communications with the PM174 from PAS software:

1. Select Configuration from the Tools menu. Under the Communication group on

the Instrument Setup tab, select the type of a connection for your device.

2. Set the device communication address you assigned to the PM174.
3. In the Sampling Rate box, select a rate at which PAS updates data on your

screen when you continuously poll the device in the PAS Data Monitor.

The communication protocol and port settings in PAS must match the settings made in

your device.
The tables below show the available options. The asterisk * shows the default settings.

COM1 settings

Code

Parameter

Options

Description

Prot

Communications protocol

ASCII, rtu*, dnP3, PrFb

ASCII, MODBUS RTU, DNP3.0 or PROFIBUS DP

protocol

rS

Port Interface, depend on order

232 = RS-232
485 = RS-485
422 = RS-422
dial = Dial-up Modem
Eth.= Ethernet
PrFb = Profibus DP

For non-serial interfaces this is not changeable, it is

automatically detected by the meter

Addr

Device Address

MODBUS: 1* -247,
DNP3.0: 0 –255 (1*)
PROFIBUS DP: 0 – 126*

bAud

Baud rate

300 - 115200 bps (19200*)

dAtA

Data format

7E, 8E (7/8 bits, even parity), 8N* (8 bits, no parity)
7E data format should not be used with the MODBUS RTU and DNP3 protocols

H.Sh

Handshaking (flow control)

nonE*=no flow control
SOFt=software (XON/XOFF)
HArd=hardware (CTS)

rtS

RTS mode

nonE* = not used
Forc = RTS is permanently asserted
CtrL = RTS is asserted during the transmission

COM2 settings

Code

Parameter

Options

Description

Prot

Communications protocol

Rtu* = MODBUS RTU
ASCII = MODBUS ASCII
dnP3 = DNP3

The communications protocol supported by the port

rS

Port Interface

485* = RS-485
422 = RS-422

Addr

Address

MODBUS: 1*-247
DNP3: 0–65532 (1*)

Device network address

bAud

Baud rate

300-115200 bps (19200*)

The port baud rate

dAtA

Data format and parity

7E, 8N*, 8E

7E data format should not be used with the Modbus

RTU and DNP3 protocols

BG0452 REV.A5