beautypg.com

Input and output ratings – SATEC PM174 Quick Start User Manual

Page 11

background image

4. In the Protocol box, select the communications protocol for the TCP port. The

meter can provide MODBUS/TCP connections on TCP port 502 and DNP3/TCP

connections on port 20000. The host port is set automatically as you select the

protocol. Select MODBUS RTU for MODBUS/TCP or DNP3 for DNP3/TCP.

5. In the Wait for Answer box, adjust the time that PAS waits for a connection

before announcing an error and the number of retries PAS uses to receive a

response from the device if communications fail.

Input and Output Ratings

DIRECT INPUT - Nominal: 690V line-to-line voltage, 790V

maximum; 400V line-to-neutral, 460V maximum - Burden:

<0.4 VA.
INPUT USING PT - Burden: <0.15 VA

690 V:

(standard)

3 voltage inputs

INPUT USING PT - Nominal: 120V line-to-line voltage, 144V

maximum - Burden: <0.04 VA

120 V: (optional)

Wire size: 2.5 - 4 mm2 (13-11 AWG)

Voltage input

terminals

INPUT VIA CT with 5A secondary output
Wire size: 2.5 to 4 mm2 (13-11 AWG) wire from CT.
Operating range: continuous 10A RMS Burden: < 0.1 VA
Overload withstand: 15A RMS continuous, 300A RMS for 1

second.

5A: (standard)

3 current inputs
(Galvanically isolated)

INPUT VIA CT with 1A secondary output
Wire size: 2.5 to 4 mm2 (13-11 AWG) wire from CT.
Operating range: continuous 2A RMS Burden: < 0.02 VA
Overload withstand: 3A RMS continuous, 80A RMS for 1

second.

1A:(optional)

Optically isolated, max. speed 115.2Kb/s

EIA RS-485

standard

Communication port

COM1

3 x wire size: 2.5 mm2 (12 AWG)

COM1 terminals

Max. speed 12 Mb/s

Profibus

Communication port

COM1 (Optional)

5 x wire size: 2.5 mm2 (12 AWG) or using terminal to DB9

converter: P/N AC0153 REV.A2

Profibus

terminals

10/100 Base T, auto adaptation speed, Max. speed 100Mb/s

Ethernet

Communication port

COM2 (Optional)

Shielded RJ45 cable

ETH connector

85-265VAC, 88-290VDC; 50/60 Hz, Burden 9VA

120/230 V

AC/DC

(standard)

Power Supply
(Galvanically isolated)

9.6-19 VDC

12 VDC

(optional)

19-37 VDC

24 VDC

(optional)

37-72 VDC

48 VDC

(optional)

3 x wire size: 2.5 to 4 mm2 (13-11 AWG)

Power Supply

input terminals

Digital inputs, relay outputs, optional analog inputs/outputs see in PM174 Installation and

Operation Manual.
PM174 models with 4DI/DO and with external split core CTs see in corresponded

addendums (BG0466 REV.A1 and BG0471 REV.A1 respectively).

BG0452 REV.A5

11