Input and output ratings – SATEC PM174 Quick Start User Manual
Page 11
![background image](/manuals/572139/11/background.png)
4. In the Protocol box, select the communications protocol for the TCP port. The
meter can provide MODBUS/TCP connections on TCP port 502 and DNP3/TCP
connections on port 20000. The host port is set automatically as you select the
protocol. Select MODBUS RTU for MODBUS/TCP or DNP3 for DNP3/TCP.
5. In the Wait for Answer box, adjust the time that PAS waits for a connection
before announcing an error and the number of retries PAS uses to receive a
response from the device if communications fail.
Input and Output Ratings
DIRECT INPUT - Nominal: 690V line-to-line voltage, 790V
maximum; 400V line-to-neutral, 460V maximum - Burden:
<0.4 VA.
INPUT USING PT - Burden: <0.15 VA
690 V:
(standard)
3 voltage inputs
INPUT USING PT - Nominal: 120V line-to-line voltage, 144V
maximum - Burden: <0.04 VA
120 V: (optional)
Wire size: 2.5 - 4 mm2 (13-11 AWG)
Voltage input
terminals
INPUT VIA CT with 5A secondary output
Wire size: 2.5 to 4 mm2 (13-11 AWG) wire from CT.
Operating range: continuous 10A RMS Burden: < 0.1 VA
Overload withstand: 15A RMS continuous, 300A RMS for 1
second.
5A: (standard)
3 current inputs
(Galvanically isolated)
INPUT VIA CT with 1A secondary output
Wire size: 2.5 to 4 mm2 (13-11 AWG) wire from CT.
Operating range: continuous 2A RMS Burden: < 0.02 VA
Overload withstand: 3A RMS continuous, 80A RMS for 1
second.
1A:(optional)
Optically isolated, max. speed 115.2Kb/s
EIA RS-485
standard
Communication port
COM1
3 x wire size: 2.5 mm2 (12 AWG)
COM1 terminals
Max. speed 12 Mb/s
Profibus
Communication port
COM1 (Optional)
5 x wire size: 2.5 mm2 (12 AWG) or using terminal to DB9
converter: P/N AC0153 REV.A2
Profibus
terminals
10/100 Base T, auto adaptation speed, Max. speed 100Mb/s
Ethernet
Communication port
COM2 (Optional)
Shielded RJ45 cable
ETH connector
85-265VAC, 88-290VDC; 50/60 Hz, Burden 9VA
120/230 V
AC/DC
(standard)
Power Supply
(Galvanically isolated)
9.6-19 VDC
12 VDC
(optional)
19-37 VDC
24 VDC
(optional)
37-72 VDC
48 VDC
(optional)
3 x wire size: 2.5 to 4 mm2 (13-11 AWG)
Power Supply
input terminals
Digital inputs, relay outputs, optional analog inputs/outputs see in PM174 Installation and
Operation Manual.
PM174 models with 4DI/DO and with external split core CTs see in corresponded
addendums (BG0466 REV.A1 and BG0471 REV.A1 respectively).
BG0452 REV.A5
11