SATEC PM174 Quick Start User Manual
Page 8
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired
option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired
option.
3. Press ENTER to confirm your changes and to store your new
setting, or press ESC to discard changes.
The table below lists the available options.
Press ESC to exit the menu.
Label Parameter
Options
Default Description
ConF
Wiring connection
(configuration) mode
3OP2
4LN3
3DIR2
4LL3
3OP3
3LN3
3LL3
3BLN3
3BLL3
4Ln3
The wiring connection of the device
Pt
PT ratio
1.0-
6500.0
1.0
The phase potential transformer’s primary to
secondary ratio
Pt.F
PT Ratio multiplier
Ч1, Ч10
Ч1
PT Ratio multiplication factor. Used in extra high
voltage networks to accommodate the PT ratio
for 500 kV and higher networks.
U.SEC Nominal secondary voltage 10-690 V 120 V
The nominal secondary line-to-neutral (in 4LN3,
3LN3 and 3BLN3 wiring modes) or line-to-line (in
4LL3, 3LL3, 3BLL3, 3OP2, 3OP3 and 3DIR
modes) voltage. Used as a reference voltage for
the IEEE 1159 Power Quality recorder.
Ct
CT primary current
1-50000 A 5 A
The primary rating of the phase current
transformer
d.P
Power block demand
period
1, 2, 3, 5,
10, 15,
20, 30, 60
min,
E=externa
l sync
30 min The length of the demand period for power
demand calculations. If the external
synchronization is selected, a pulse front on the
digital input DI1 denotes the start of the demand
interval.
nd.P
The number of blocks in
the sliding window
1-15
1
The number of blocks to be averaged for sliding
window demands
Ad.P
Ampere, volt and THD
demand period
0-1800
sec
900 sec The length of the demand period for ampere, volt
and THD demand calculations
Freq
Nominal frequency
50,60 Hz 60 Hz
The nominal line frequency
LoAd
Maximum demand load
current
0-50000 A 0
The maximum demand load current (0 = CT
primary)
Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs.
The maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the
product is greater, power readings are zeroed.
bASc
4Ln3
ConF
BG0452 REV.A5
8