To select a setup option:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the desired

option.


To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the desired

option.

3. Press ENTER to confirm your changes and to store your new

setting, or press ESC to discard changes.

The table below lists the available options.
Press ESC to exit the menu.

Label Parameter

Options

Default Description

ConF

Wiring connection

(configuration) mode

3OP2

4LN3

3DIR2

4LL3

3OP3

3LN3

3LL3

3BLN3

3BLL3

4Ln3

The wiring connection of the device

Pt

PT ratio

1.0-

6500.0

1.0

The phase potential transformer’s primary to

secondary ratio

Pt.F

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor. Used in extra high

voltage networks to accommodate the PT ratio

for 500 kV and higher networks.

U.SEC Nominal secondary voltage 10-690 V 120 V

The nominal secondary line-to-neutral (in 4LN3,

3LN3 and 3BLN3 wiring modes) or line-to-line (in

4LL3, 3LL3, 3BLL3, 3OP2, 3OP3 and 3DIR

modes) voltage. Used as a reference voltage for

the IEEE 1159 Power Quality recorder.

Ct

CT primary current

1-50000 A 5 A

The primary rating of the phase current

transformer

d.P

Power block demand

period

1, 2, 3, 5,

10, 15,

20, 30, 60

min,

E=externa

l sync

30 min The length of the demand period for power

demand calculations. If the external

synchronization is selected, a pulse front on the

digital input DI1 denotes the start of the demand

interval.

nd.P

The number of blocks in

the sliding window

1-15

1

The number of blocks to be averaged for sliding

window demands

Ad.P

Ampere, volt and THD

demand period

0-1800

sec

900 sec The length of the demand period for ampere, volt

and THD demand calculations

Freq

Nominal frequency

50,60 Hz 60 Hz

The nominal line frequency

LoAd

Maximum demand load

current

0-50000 A 0

The maximum demand load current (0 = CT

primary)

Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs.

The maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the

product is greater, power readings are zeroed.

bASc

4Ln3

ConF

BG0452 REV.A5

8