RKI Instruments Digester Gas Monitor User Manual
Page 54

48 • Viewing and Changing Global Parameters
Digester Gas Monitor Operator’s Manual
2.
Press and release the UP/YES button to continue in the Global Menu to the Cycle
Interval Time screen.
3.
Use the UP/YES and DOWN/NO buttons to set the cycle interval time. It can be set to
15 minutes, 1 hour, 4 hours, 8 hours, or 24 hours.
4.
Press ENTER to save the changes and continue to the STROBE Installation screen.
5.
Use the UP/YES and DOWN/NO buttons to toggle between NO STROBE INSTALLED
and STROBE INSTALLED.
6.
Press ENTER to save the changes and continue to the Normal Relay States screen.
Press the ESCAPE button to go back to the Cycle Interval Time screen.
7.
The Normal Relay States screen will be displayed.
8.
Use the UP/YES and DOWN/NO buttons to toggle between NORM ENERGIZED and
NORM DE-ENERGIZED.
9.
Press ENTER to save the changes and continue to the Alarm Buzzer Silence screen.
Press the ESCAPE button to go back to the STROBE Installation Screen.
10. Use the UP/YES and DOWN/NO buttons to toggle between CAN SILENCE BUZZER
and CAN’T SILENCE BUZZER.
Cycle Interval Time:
1 HOUR
UP / DN then ENT / ESC
STROBE Installation:
STROBE IS INSTALLED
UP / DN then ENT / ESC
NORMAL RELAY STATES:
NORM DE-ENERGIZED
UP / DN then ENT / ESC
ALARM BUZZ SILENCE:
CAN SILENCE BUZZER
UP / DN then ENT / ESC