RKI Instruments 12 VDC Beacon 200 User Manual
Page 29
12 VDC Beacon 200 Operator’s Manual • 25
NOTE: To silence the buzzer while in an alarm 1 condition, press the
reset switch.
You cannot de-energize the alarm 1 relays and consequently the
strobe/horn until the gas reading falls below the alarm 1 setpoint.
Alarm 2 Condition
This section describes the audible and visual indications for an alarm 2
condition and suggests response to an alarm 2 condition.
Alarm 2 Condition Indications
When the gas reading of an active channel reaches the alarm 2 setpoint,
the 12 VDC Beacon 200 senses an alarm 2 condition. The 12 VDC Beacon
200 alerts you to an alarm 2 condition as follows:
•
The ALARM 2 light turns on.
•
The gas reading in alarm 2 condition continues to flash and alternates
with the ALARM-2 messages.
•
The buzzer sounds a Pulsing tone.
•
The common alarm 2 relay energizes.
•
The applicable alarm 2 channel relay energizes.
Responding to an Alarm 2 Condition
This section suggests response to an alarm 2 condition.
1. Follow your established procedure for a high level combustible or toxic
gas condition or an increasing oxygen content condition.
2. Oxygen alarms are self-resetting and will automatically clear when the
oxygen rises above the alarm 2 setpoint.
3. Alarms for all other gas types are latching. After the gas reading falls
below the alarm 2 setpoint, press the reset switch to reset the alarm
circuit. Resetting the alarm circuit turns off the ALARM 2 light, and de-
energizes the common and channel alarm 2 relays.
NOTE: To silence the buzzer while in an alarm 2 condition, press the
reset switch.
You cannot de-energize the alarm 2 relays until the gas reading
falls below the alarm 2 setpoint.