Communication and control, Ul cl2p ul cmp csa cmp ft4 – Northern Connectors Alpha Wire Communication, Control & Industrial Cable User Manual
Page 90
Alpha Wire | www.alphawire.com | 1-800-52 ALPHA
Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.
362
Cable > Communication, Control and Industrial > Multipair > Foil Shield > 300 V
Communication and Control
300/150 V Foil Shield, Multipair, PVC, PVC
Plenum Rated
UL CL2P
UL CMP
CSA CMP FT4
Operating Temperature
• -5°C to +75°C
Conductor Color Coding
• Chart A1 (page 516)
Materials
• Stranded bare copper
conductors
• Plenum-rated PVC insulation
• Foil shield
• Aluminum/polyester foil shield,
25% overlap min.
Foil facing outward
Stranded tinned copper drain
wire (see tables for size)
• Slate plenum-rated PVC jacket
Availability
500 ft (152 m)
1000 ft (305 m)
24 AWG (0.22 mm
2
)
Stranding: 7/32 (7 x 0.20 mm)
Insulation thickness: 0.008 (0.020 mm)
24 AWG (0.22 mm
2
) drain wire
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
57602
2
0.165
4.19
0.015
0.39
57603
3
0.175
4.45
0.015
0.39
57604
4
0.193
4.90
0.015
0.39
57605
5
0.212
5.38
0.015
0.39
57606
6
0.231
5.87
0.015
0.39
22 AWG (0.35 mm
2
)
Stranding: 7/30 (7 x 0.25 mm)
Insulation thickness: 0.008 (0.020 mm)
24 AWG (0.22 mm
2
) drain wire
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
58412
2
0.185
4.70
0.015
0.39
58413
3
0.197
5.00
0.015
0.39
58414
4
0.217
5.51
0.015
0.39
58415
5
0.239
6.07
0.015
0.39
58416
6
0.261
6.63
0.015
0.39
57628
8
0.285
7.24
0.015
0.39
58419
9
0.311
7.90
0.016
0.41
58420/19
19
0.418
10.62
0.018
0.46
20 AWG (0.35 mm
2
)
Stranding: 7/0.0121 (7 x 0.31 mm)
Insulation thickness: 0.008 (0.020 mm)
22 AWG (0.35 mm
2
) drain wire
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
57632
2
0.205
5.21
0.015
0.39
57634
4
0.240
6.10
0.015
0.39
57636
6
0.291
7.39
0.015
0.39