Communication and control, 300 v overall foil shield, multipair, sr-pvc, pvc – Northern Connectors Alpha Wire Communication, Control & Industrial Cable User Manual
Page 66
Alpha Wire | www.alphawire.com | 1-800-52 ALPHA
Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.
338
Cable > Communication, Control and Industrial > Multipair > Overall Foil Shield > 300 V
Communication and Control
300 V Overall Foil Shield, Multipair, SR-PVC, PVC
UL AWM 2464
UL CM
CSA CMG FT4
Operating Temperature
• -20°C to +80°C (AWM)
• -20°C to +75°C (CM)
• -20°C to +60°C (CMG)
Conductor Color Coding
• Chart K (page 517)
Materials
• Stranded tinned copper
conductors
• Semirigid PVC insulation
• Aluminum/polyester foil shield,
25% overlap min.
Foil facing inward
Stranded tinned copper drain
wire equal in size to conductor
• Slate PVC jacket
Availability
100 ft (30.5 m)
500 ft (152 m)
1000 ft (305 m)
24 AWG (0.23 mm
2
)
Stranding: 7/32 (7 x 0.20 mm)
Insulation thickness: 0.010 (0.25 mm)
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
5471C
1
0.156
3.96
0.032
0.81
5472C
2
0.212
5.38
0.032
0.81
5473C
3
0.224
5.69
0.032
0.81
5474C
4
0.243
6.17
0.032
0.81
5475C
5
0.270
6.86
0.035
0.89
5476C
6
0.292
7.42
0.035
0.89
5477C
7
0.292
7.42
0.035
0.89
5478C
8
0.316
8.03
0.035
0.89
5479C
9
0.343
8.71
0.037
0.83
5480C
10
0.373
9.47
0.040
1.02
5480/15C
15
0.415
10.54
0.040
1.02
5480/19C
19
0.445
11.30
0.040
1.02
5480/25C
25
0.527
13.39
0.045
1.14
5480/50C *
50
0.699
17.75
0.053
1.35
*Color code chart C.
Individually Shielded, 22 AWG (0.35 mm
2
), 7/30 (7 x .025) Tinned Copper Drain Wire
UL VW-1
20 AWG (0.56 mm
2
)
Stranding: 7/28 (7 x 0.33 mm)
Insulation thickness: 0.010 (0.25 mm)
Part No.
Pairs
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
6416
2
0.295
7.49
0.041
1.04
Mutual capacitance: 55 pF/ft (180 pF/m)