Solar cable, 1000 v unshielded, multiconductor, pvc/nylon, pvc – Northern Connectors Alpha Wire Communication, Control & Industrial Cable User Manual
Page 19
Alpha Wire | www.alphawire.com | 1-800-52 ALPHA
Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.
291
Cable > Communication, Control and Industrial > Multiconductor > Unshielded > 1000 V
Solar Cable
1000 V Unshielded, Multiconductor, PVC/Nylon, PVC
UL TC-ER
UL WTTC (1000 V)
UL MTW
CSA AWM I/II A/B FT1
Operating Temperature
• -40°C to +90°C (static)
• -30°C to +90°C (dynamic)
• +105°C (CSA)
Conductor Color Coding
• Chart F (page 520)
Materials
• Stranded bare copper
conductors
• PVC/nylon insulation
• Clear polyester wrap
• Green PVC jacket
Features
• UL Sunlight Resistant
• UL Oil Res. I
• UL Direct Burial
• Suitable for use in Class I,
Division 2 locations per Article
501 of the National Electric Code
Availability
Bulk, cut to length
FIT® Tubing Recommendations
• FIT-260: Cross-linked polyolefin
for ground identification
• FIT-300: Dual-wall polyolefin
with meltable inner wall
• FIT-750: Bonding adhesive-lined
cross-linked polyolefin
18 AWG (0.96 mm
2
)
Stranding: 19/30 (19 x 0.25 mm)
Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.12 mm) nylon
Part No.
Conductors
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
SPM1803
3
0.301
7.65
0.050
1.27
SPM1804
4
0.326
8.28
0.050
1.27
SPM1805
5
0.353
8.97
0.050
1.27
SPM1807
7
0.381
9.68
0.050
1.27
SPM1809
9
0.438
11.13
0.050
1.27
12 AWG (3.29 mm
2
)
Stranding: 65/30 (65 x 0.25 mm)
Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.12 mm) nylon
Part No.
Conductors
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
SPM1203
3
0.394
10.01
0.050
1.27
SPM1204
4
0.430
10.92
0.050
1.27
SPM1205
5
0.469
11.91
0.050
1.27
SPM1207
7
0.510
12.95
0.050
1.27
SPM1209
9
0.625
15.88
0.065
1.65
16 AWG (1.32 mm
2
)
Stranding: 26/30 (26 x 0.25 mm)
Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.12 mm) nylon
Part No.
Conductors
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
SPM1603
3
0.323
8.20
0.050
1.27
SPM1604
4
0.350
8.89
0.050
1.27
SPM1605
5
0.380
9.65
0.050
1.27
SPM1607
7
0.411
10.44
0.050
1.27
SPM1609
9
0.475
12.07
0.050
1.27
14 AWG (2.08 mm
2
)
Stranding: 41/30 (41 x 0.25 mm)
Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.12 mm) nylon
Part No.
Conductors
Nominal Diameter
Jacket Thickness
Inch
mm
Inch
mm
SPM1403
3
0.353
8.97
0.050
1.27
SPM1404
4
0.384
9.75
0.050
1.27
SPM1405
5
0.418
10.62
0.050
1.27
SPM1407
7
0.453
11.51
0.050
1.27
SPM1409
9
0.556
14.12
0.065
1.65