beautypg.com

J3a/b connectors, J3a/b connectors 17 – MTS Isolation Service Manifold Controller User Manual

Page 17

background image

J3A/B Connectors

Isolation Service Manifold Controller

Hardware Overview

17

J3A/B Connectors

Function

Channel A and B ISM control connector to provide connection to the ISM
Isolation and Bypass solenoids, Isolation valve position switch, and Isolation
output pressure switch.

Connector Type

Stacked D25S/D25S (reference cable 574745-XX)

Pin Outs/Electrical

specifications

Pin

Description

1

Bypass Solenoid Control output.

Bypass solenoid control output.

2

Bypass Solenoid Control return.

Signal return for bypass solenoid control.

3 and 16

Isolation Solenoid Control output.

Isolation solenoid control output.

4

Isolation Solenoid Control return.

Signal return for Isolation solenoid control output

5

Isolation output pressure switch input.

Pressure switch connects between pin's 5 and 6 in
this connector.

6

Isolation output pressure switch power output power.

Provides power to pass through isolation output
pressure switch to isolation output pressure switch
input on pin 5.

7

Isolation valve position input.

Position switch connects between pin's 7 and 8 in
this connector.

8

Isolation valve position switch power output power.

Provides power to pass through isolation output
valve position switch to isolation output valve
position switch input on pin 7.

9 through 15,
17 through 25

Not used.