Troubleshooting and fault elimination
System error messages
General error messages
l
35
EDKVF93−04 EN 2.0
4.5
System error messages
4.5.1
General error messages
)
Note!
If you use GDC or a fieldbus module to retrieve the fault (C0168/x), the error
message will be represented by an error number.
Display Error number
x = 0: TRIP
x = 1: Message
x = 2: Warning
Error
Cause
Remedy
−−−
−−−
No fault
—
—
CCr
x071
System fault
Processor is overloaded or there is a
fault in the program processing
Reduce processor load. Remove function
blocks that are not needed from the
processing table
Strong interference on control cables
Shield control cables
Ground or earth loops in the wiring
Check wiring
CE0
x061
Communication
error
Fault during transmission of control
commands via automation interface X1
Plug in automation module firmly, bolt
down, if necessary
CE1
x062
Communication
error at the process
data input object
CAN−IN1
CAN−IN1 object receives faulty data, or
communication is interrupted
l
Check cable at X4
l
Check sender
l
Increase monitoring time under
C0357/1 if necessary
CE2
x063
Communication
error at the process
data input object
CAN−IN2
CAN−IN2 object receives faulty data, or
communication is interrupted
l
Check cable at X4
l
Check sender
l
Increase monitoring time under
C0357/2 if necessary
CE3
x064
Communication
error at the process
data input object
CAN−IN3
CAN−IN3 object receives faulty data, or
communication is interrupted
l
Check cable at X4
l
Check sender
l
Increase monitoring time under
C0357/3 if necessary
CE4
x065
BUS−OFF state
Controller has received too many
incorrect telegrams via system bus X4,
and has disconnected from the bus
l
Check wiring
l
Check bus termination (if any)
l
Check shield contact of the cables
l
Check PE connection
l
Check bus load
l
Reduce baud rate (observe cable
length)
EEr
x091
External fault
(TRIP−Set)
A digital input assigned with TRIP−set
function has been activated (in the most
basic configurations the input X5/E4 is
LOW−active and linked with the TRIP−set
function)
l
Check external encoder
l
Check signal at the digital input
X5/E4:
– Either connect HIGH level or
– Change polarity in C0114 to
HIGH−active. CAUTION! When
changing to HIGH level, the
wire−break protection gets lost.
The two terminal strips at X5 are
reversed
Check the position of the terminal
strips:
l
If you look at the connection unit in
reading direction, the left terminal
strip X5 must be connected with the
input signals and the right terminal
strip X5 must be connected with the
output signals.
H05
x105
Internal fault
Contact Lenze
H07
x107
Wrong power
stage
During initialisation of the controller, a
wrong power stage was detected
Contact Lenze