2 supply-failure control (l_mfail), Supply−failure control (l_mfail), Function block library lenze9300servo.lib – Lenze DDS Function library 9300 Servo User Manual
Page 16: 2 supply−failure control (l_mfail), Parameter codes of the instances

Function block library Lenze9300Servo.lib
Special functions
2.1.2
Supply−failure control (L_MFAIL)
2−6
L
Lenze9300Servo.lib EN 1.1
2.1.2
Supply−failure control (L_MFAIL)
If the supply voltage via L1, L2, L3 or +UG, −UG fails, then the drive (drive network) can be decelerated
(braked) in a controlled manner.
Without this function, the drive (drive network) would coast down.
MCTRL_nDCVolt_a
L_MFAIL
nVp
nAdapt_a
nConst_a
nTi
nDCSet_a
nNSet_a
bFault_b
bReset_b
nThreshold_a
nNAct_a
nSet_a
CTRL
0
1
nNOut_a
wRetriggerTime
bStatus_b
bIReset_b
nTn
Abb. 2−6
Supply−failure control (L_MFAIL)
VariableName
DataType
SignalType
VariableType
Note
nAdapt_a
Integer
analog
VAR_INPUT
Dynamic adjustment of the proportional gain of the
U
Gsetp
−control in [%] of
nVp . (16384 º 100 %)
nConst_a
Integer
analog
VAR_INPUT
Proportional gain of the U
Gsetp
controller in [%]
from
nVp . (16384 º 100 %)
nDcSet_a
Integer
analog
VAR_INPUT
Voltage setpoint at which the DC bus voltage is to be
maintained. (1000 V
º 100 %)
nNSet_a
Integer
analog
VAR_INPUT
Speed setpoint in [%] of C0011
(C0011
º 100 % º 16384)
bFault_b
Bool
binary
VAR_INPUT
TRUE = activates the supply−failure control
bReset_b
Bool
binary
VAR_INPUT
TRUE = reset
nThreshold_a
Integer
analog
VAR_INPUT
Restart threshold in [%] of C0011
(C0011
º 100 % º 16384)
nNAct_a
Integer
analog
VAR_INPUT
Comparison value for the restart threshold in [%] of
C0011
nSet_a
Integer
analog
VAR_INPUT
Speed starting point for run−down/deceleration in [%]
of C0011
(C0011
º 100 % º 16384)
nNOut_a
Integer
analog
VAR_OUTPUT
Speed setpoint in [%] of C0011
(C0011
º 100 % º 16384)
bStatus_b
Bool
binary
VAR_OUTPUT
TRUE = supply−failure control is active
bIReset_b
Bool
binary
VAR_OUTPUT
TRUE = supply−failure control active, the drive is
braking
nVp
Integer
−
VAR CONSTANT RETAIN
Gain
nTn
Integer
−
VAR CONSTANT RETAIN
Integral−action time T
nTi
Integer
−
VAR CONSTANT RETAIN
Acceleration time
wRetriggerTime
Unsigned
Integer
−
VAR CONSTANT RETAIN
Retrigger time
Parameter codes of the instances
VariableName
L_MFAIL1
SettingRange
Lenze
nVp
C0980
0.001 ... 31.000
0.500
nTn
C0981
20 ... 2000 ms
100
nTi
C0982
0.001 ... 16.000 s
2.000
wRetriggerTime
C0983
0.001 ... 60.000 s
1.000