4 technical data, 1 general data and operating conditions, Technical data – Lenze E82ZN User Manual
Page 29: General data and operating conditions, 4technical data

Technical data
General data and operating conditions
4
l
29
EDK82ZN903 DE/EN/FR 5.1
4
Technical data
4.1
General data and operating conditions
Standards
Approval
UL
UL 508, Standard for Electromagnetic Interference Filters
(File No. E219022) for USA and Canada
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
Without grounded neutral
Max. mains voltage 400 V!
Observe instructions for special measures in the
documentation for the basic device!
IT systems
Operation is not permissible.
Protection
Type of protection
EN 60529
IP 20
Not in the wire range of
the terminals
NEMA 250
Protection against contact to
type 1
Insulation resistance
EN 61800−5−1
Overvoltage category III
> 2000 m: Overvoltage category II
Leakage current
EN 61800−5−1
> 3.5 mA
Observe regulations and
safety instructions!
Protective device
Type
Thermal contact, potential−free
NC contact
Function
Monitoring the internal
temperature of the device
Switching threshold
140 °C
Switching capacity
250 V / 1.6 A
Ambient conditions
Temperature
Storage
−25 ... +60 °C
Transport
−25 ... +70 °C
Operation
−10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m
Pollution
EN 61800−5−1
Pollution degree 2
Vibration resistance
EN 50178; IEC
61800−5−1;
Germanischer Lloyd,
general conditions
Acceleration−resistant up to 0.7 g