Troubleshooting and fault elimination – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual
Page 161

Troubleshooting and fault elimination
Fault elimination
Fault messages
l
161
EDK82EV222 DE/EN/FR 13.0
Remedy
Cause
Fault
PC
1)
Keypad
OH
a
50
Heatsink
temperature > +85
°C
Ambient temperature is too high
Allow controller to cool and provide
for better ventilation
OH
e
−
Heatsink
temperature > +80
°C
Heatsink is very dirty
Clean heatsink
OH
e
−
Heatsink
temperature > +80
°C
Impermissible high currents or
frequent and too long
acceleration processes
l
Check drive dimensioning
l
Check load, replace
rough−running, defective
bearings, if necessary
OH3
a
53
PTC monitoring
(TRIP)
(display when
C0119 = 1 or 4)
Motor too hot due to
impermissible high currents or
frequent and too long
acceleration processes
Check drive dimensioning
No PTC connected
Connect PTC or switch off monitoring
OH4
a
54
Controller
overtemperature
Controller is too hot inside
l
Reduce controller load
l
Improve cooling
l
Check fan in the controller
OH51
203
PTC monitoring
(display when
C0119 = 2 or 5)
Motor too hot due to
impermissible high currents or
frequent and too long
acceleration processes
Check drive dimensioning
No PTC connected
Connect PTC or switch off monitoring
OU
c
−
DC−bus overvoltage
(message or TRIP
configurable in
C0310)
Mains voltage is too high
Check supply voltage
OUE
a
22
Braking operation
l
Increase deceleration times
l
For operation with an external
brake resistor:
– Check dimensioning,
connection and supply cable of
the brake resistor
– Increase deceleration times
Earth leakage at motor end
Check motor supply cable and motor
for earth fault (disconnect motor
from the inverter)