Mains connection, Electrical installation, Stop – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual
Page 120

Electrical installation
Mains connection
Connection plan for controllers type E82xVxxxK2C (230/240 V mains)
l
120
EDK82EV222 DE/EN/FR 13.0
Mains connection
Connection plan for controllers type E82xVxxxK2C (230/240 V mains)
(
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
^ Technical data). A
higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter. This
requirement can differ with regard to operation at rated power and operation at an
increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
fixed installation is required. The PE conductor has to be designed double.
E82EV551K2C
E82EV751K2C
X1.1
X1.1
E82EV251K2C
E82EV371K2C
E82EV152K2C
E82EV222K2C
X1.1
N
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
PE
L1
1/N/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1
PE
L2
PE
L1
2/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1
PE
PE
L1
L2
L3
3/PE AC 230 V/240 V
+UG -UG
L1
L2/N L3/N
L1
PE
PE
L1
L2
2/PE AC 230 V/240 V
+UG -UG
L1
L3 PE
L2/N
PE
L1
N
1/N/PE AC 230 V/240 V
+UG -UG
L1
L2/N
L3 PE
PE
L1
N
1/N/PE AC 230 V/240 V
L1
L2/N
PE
L2/N
PE
L1
L2
L3
3/PE AC 230 V/240 V
+UG -UG
L1
L3 PE
2/PE AC 230 V/240 V
PE
L1
L1
L2/N
PE
L2
0
0
8200vec012
0
Route two cables with 1.5 mm
2
each to the terminals!
X1.1/+UG, X1.1/−UG
Supply for DC−bus operation