2 protective insulation, Protective insulation, Against accidental contact. (see chapter "4.2 – Lenze EMF2191IB User Manual
Page 18: Technical data, Danger

Technical data
Protective insulation
l
18
EDSMF2191IB EN 2.0
4.2
Protective insulation
{
Danger!
Dangerous electrical voltage
If Lenze controllers are used on a phase earthed mains with a rated mains
voltage
³ 400 V, protection against accidental contact is not ensured without
implementing external measures.
Possible consequences:
ƒ
Death or serious injury
Protective measures:
ƒ
If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
– a double isolating distance must exist.
– the components to be connected must be provided with the second
isolating distance.
Insulation between bus and ...
Type of insulation
(in accordance with EN 61800−5−1)
l
Earth reference / PE
Functional insulation
l
With external supply
Functional insulation
l
Power stage
– 8200 vector
Reinforced insulation
– 9300 servo inverter
Reinforced insulation
– 93xx servo position controller
Reinforced insulation
– 93xx servo register control
Reinforced insulation
– 93xx servo cam profiler
Reinforced insulation
– 9300 vector / Servo PLC
Reinforced insulation
– ECS devices
Reinforced insulation
l
Control terminals
– 8200 vector
Functional insulation
– 9300 servo inverter
Basic insulation
– 93xx servo position controller
Basic insulation
– 93xx servo register control
Basic insulation
– 93xx servo cam profiler
Basic insulation
– 9300 vector / Servo PLC
Basic insulation
– ECS devices
Basic insulation