C13207 | response in case of communication fault, C13208 | as-i monitoring times, C13210 | as-i bus transaction counter – Lenze E84DGFCA User Manual
Page 63: C13207/1, C13208/1, C13207/2, C13208/2, C13207/3, C13208/3, Parameter reference

Parameter reference
Parameters relevant for AS-i communication
63
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13207
C13208
C13210
Parameter | Name:
C13207 | Response in case of communication fault
Data type: UNSIGNED_8
Index: 11368 = 0x2C68
The response set here is triggered if the AS-i node does not receive a message from the master within the
monitoring time (
) or detects that it has exited the DATA_EXCHANGE status.
A change in the monitoring response becomes immediately effective.
Selection list
(Lenze setting printed in bold)
0 No response
1 Fault
4 Warning Locked
Subcodes
Lenze setting
Info
C13207/1
1
Slave 1 communication timeout
C13207/2
1
Slave 1 communication timeout - CTT2 extended cyclic
C13207/3
1
Slave 2 communication timeout
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13208 | AS-i monitoring times
Data type: UNSIGNED_16
Index: 11367 = 0x2C67
If the DATA_EXCHANGE status is exited, the response parameterised in
is carried out when the time
set here for the data exchange has elapsed.
• The value "65535" is used to deactivate the monitoring.
• A change in the monitoring is immediately effective.
Setting range
(min. value | unit | max. value)
0
ms
65535
Subcodes
Lenze setting
Info
C13208/1
3000 ms
Slave 1 monitoring time
C13208/2
3000 ms
Slave 1 monitoring time - CTT2 extended cyclic
C13208/3
3000 ms
Slave 2 monitoring time
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13210 | AS-i Bus transaction counter
Data type: UNSIGNED_16
Index: 11365 = 0x2C65
Display of AS-i transactions
Display range
(min. value | unit | max. value)
0
65535
Subcodes
Info
C13210/1
Slave 1 - Data cycles
C13210/2
Slave 1 - Parameter cycles
C13210/3
Slave 1 - CTT2 extended cyclic cycles
C13210/4
Slave 1 - CTT2 acyclic access cycles
C13210/5
Slave 2 - Data cycles
C13210/6
Slave 2 - Parameter cycles
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT