4.3
Communication time
The communication time defines the time between the start of a request and the arrival of the
corresponding response.
The communication times in an AS-i network depend on the ...
• processing time in the inverter;
• telegram runtime (baud rate / telegram length);
• nesting depth of the network.
Processing time in the inverter
There are no interdependencies between parameter data and process data.
Data
Processing time
Process data
approx. 2 ms
+ 0 ... 1 ms
+ 1 ... x ms
Update cycle
Processing time in the module
Application task runtime of the use technology application
(tolerance)
Parameter data
approx. 30 ms + a tolerance of 20 ms (typically)
For some codes, the processing time may be longer (see software manual/
»Engineer« online help "Inverter Drives 8400 motec").