0x01bc6102, 0x01bc813a, 0x01bc813b – Lenze E84DGFCA User Manual
Page 58: 0x01bc813c, Error messages

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013
58
Error messages
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Module parameter access failure [0x01bc6102]
Slave 1 data exchange timeout [0x01bc813a]
Slave 1 CTT2 extended cyclic timeout [0x01bc813b]
Slave 2 data exchange timeout [0x01bc813c]
Response (Lenze setting printed in bold)
Setting:
/
( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• AS-i voltage supply interrupted.
• Connection between the Communication Unit and
the Drive Unit defective.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• If this error continues to occur, please contact the
Lenze service. (it might be necessary to replace the
Communication Unit.)
Response (Lenze setting printed in bold)
Setting:
/
( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• AS-i communication / voltage supply interrupted.
• The monitoring time is too low.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• Check and raise the monitoring time.
• Check and adjust the AS-i settings of the master.
• Check and adjust the AS-i profile settings of the
master and the slaves.
Response (Lenze setting printed in bold)
Setting:
/
( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• AS-i communication / voltage supply interrupted.
• The monitoring time is too low.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• Check and raise the monitoring time.
• Check and adjust the CTT2 settings of the master.
• Check and adjust the AS-i profile settings of the
master and the slaves.
Response (Lenze setting printed in bold)
Setting:
/
( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• AS-i communication / voltage supply interrupted.
• The monitoring time is too low.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• Check and raise the monitoring time.
• Check and adjust the AS-i settings of the master.
• Check and adjust the AS-i profile settings of the
master and the slaves.