Safety instructions
Residual hazards
l
31
EDK94AZRS6 DE/EN/FR/ES/IT 7.0
2.2
Residual hazards
{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
O
Warnings!
Conditions of Acceptability:
ƒ
The products covered by this report are only intended for use
with Power Conversion Equipment (inverters).
ƒ
Consideration shall be given to the field wiring leads. No strain
relief test was performed on the leads.
ƒ
The devices in this report are only evaluated for factory wiring
use.
ƒ
Temperature tests were performed with hook mounted drive.
ƒ
Reactor model E94AZR0544 shall be installed with input wiring
of 4 AWG minimum. Reactor model E94AZR0954 shall be
installed with input wiring of 1/0 AWG minimum.