Electrical installation, Important notes, 6electrical installation – Lenze E94AZRS0294 User Manual
Page 50

6
Electrical installation
Important notes
EDK94AZRS DE/EN/FR/ES/IT 6.0
50
l
H1_E_INST−Fi Verdraht
6
Electrical installation
Important notes
ƒ Installation must
– always be in accordance with the operating conditions specified in the Technical
data (
^ 40).
– be carried out to EN 60204−1.
ƒ Please observe the following when selecting the cable type:
– The cables used must comply with the approvals required for the application (e. g.
VDE, UL etc.).
– Fuses and cable cross−sections must be dimensioned in accordance with the
specifications in the documentation for the basic device.
{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes before
working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
{
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ
Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
³ 10 mm
2
or PE conductor must be connected twice)