2 technical data, Technical data 2, 2technical data – Lenze EZS3-xxxA200 Sinusoidal filter 115-150A User Manual
Page 15
Technical data
2
l
15
EDKZS3Y200 DE/EN/FR/ES/IT 1.1
2
Technical data
Standards
Conformity
CE
Low−Voltage Directive
Approval
UR
UL508, Industrial Control
Equipment, Underwriter
Laboratories (File−No. E219022) for
USA and Canada
Operating conditions
Climatic conditions
Class 3K3 according to EN 50178
Without condensation, average
relative humidity 85 %
Permissible ambient
operating temperature
−10 °C ... +55 °C
Above 40 °C, the rated current I
r
must be reduced by 2.5 %/°C
Permissible installation
height
0 ... 4000 m amsl
Above 1000 m, the rated current I
r
must be reduced by 5 %/1000 m
Vibration resistance
Accelerational stability up to 1 g
EN50178, IEC61800−5−1 and
Germanischer Lloyd, general
conditions
Degree of protection
IP20 (protection against contact to NEMA 250 type 1)
Mounting position
Vertical with fixing bracket below
Connecting cables
Controller
« filter
As short as possible, shielded
Filter
« motor Max. 200 m shielded or max. 300 m unshielded
Rated data
Type
U
[V]
f
ch
[kHz]
I
r
[A]
P
V
[W]
L
[mH]
m
[kg]
EZS3−115A200
0 ... 550 V AC
2 ... 4
115
360
0.7
66
EZS3−150A200
150
400
0.5
69
U
Voltage range
PV
Power loss
f
ch
Switching frequency
L
Inductance
I
r
Rated current
m