Trouble shooting & fault elimination – Lenze SMD 0-37kW-22kW User Manual
Page 23
Lenze 13466184 EDBSL03 v20
EN, DE, FR, IT, ES
21
Trouble Shooting & Fault Elimination
Error
Cause
Remedy
(1)
0C1
Short-circuit or overload
Short-circuit
Find reason for short-circuit; check
motor cable
Excessive capacitive charging
current of the motor cable
Use shorter motor cables with lower
charging current
Acceleration time (C12, c01) too
short
• Increase acceleration time
• Check controller selection
Defective motor cable
Check wiring
Internal fault in motor
Check motor
Frequent and long overload
Check controller selection
0C2
Earth fault
Grounded motor phase
Check motor/motor cable
Excessive capacitive charging
current of the motor cable
Use shorter motor cables with lower
charging current
0C6
Motor overload (I
2
t overload)
Motor is thermally overloaded,
due to:
• impermissable continuous current
• frequent or too long acceleration
processes
• Check controller selection
• Check setting of c20
0H
Controller overtemperature
Controller too hot inside
• Reduce controller load
• Improve cooling
OU
Overvoltage on DC bus
Mains voltage too high
Check mains voltage
Excessively short deceleration time
or motor in generator mode
Increase deceleration time or use
dynamic braking option
Earth leakage on the motor side
Check motor/motor cable
(separate motor from controller)
rSt
Faulty auto-TRIP reset
More than 8 errors in 10 minutes
Depends on the error
Sd5
Loss of 4-20 mA reference
4-20 mA signal is below 2 mA
(C34 = 4)
Check signal/signal wire
SF
Single phase fault
A mains phase has been lost
Check mains voltage
(1) The drive can only be restarted if the error message has been reset; see c70
NOTE
In the event of an “OC6” (Motor Overload) failure there is a 3-minute delay before
resetting is possible. This is a requirement of UL508C. This delay is intended to
allow time for the motor to cool.
If power is removed when the drive is in an “OC6” fault state, when the power is
restored the “OC6” fault will still be present and the delay will still be active even if
power was removed for longer than 3 minutes.