beautypg.com

Commissioning – Lenze SMD 0-37kW-22kW User Manual

Page 17

background image

Lenze 13466184 EDBSL03 v20

EN, DE, FR, IT, ES

15

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C10

Minimum output

frequency

0.0 0.0 {Hz} 500 • Output frequency at 0% analog

setpoint

• C10 not active for fixed setpoints or

setpoint selection via c40

C11

Maximum output

frequency

50.0 7.5 {Hz} 500 • Output frequency at 100% analog

setpoint

• C11 is never exceeded

WARNING!

Consult motor/machine manufacturer before operating above rated frequency.

Overspeeding the motor/machine may cause damage to equipment and injury to

personnel!

C12

Acceleration time 1

5.0 0.0 {s} 999 • C12 = frequency change 0 Hz...C11

• C13 = frequency change C11...0 Hz

• For S-ramp accel/decel, adjust c82

C13

Deceleration time 1

5.0 0.0 {s} 999

C14

Operating Mode

2

0 Linear characteristic with

Auto-Boost

• Linear characteristic: for standard

applications

• Square-law characteristic: for fans

and pumps with square-law load

characteristic

• Auto boost: load-dependent output

voltage for low-loss operation

1 Square-law characteristic with

Auto-Boost

2 Linear characteristic with constant

V

min

boost

3 Square-law characteristic with

constant V

min

boost

C15

V/f reference point

50.0 25.0 {Hz} 999

Set the rated motor frequency

(nameplate) for standard applications

C16

V

min

boost

(optimization of

torque behavior)

4.0 0.0 {%} 40.0

Set after commissioning: The unloaded

motor should run at slip frequency

(approx. 5 Hz), increase C16 until

motor current (C54) = 0.8 x rated motor

current

C17

Frequency threshold

(Q

min

)

0.0 0.0 {Hz} 500 See C08 and c17, selection 7

Reference: setpoint

C18

Chopper frequency

2

0 4 kHz

• As chopper frequency is increased,

motor noise is decreased

• Observe derating in Section 2.2

• Automatic derating to 4 kHz at 1.2 x I

r

1 6 kHz
2 8 kHz
3 10 kHz

C21

Slip compensation

0.0 0.0 {%} 40.0 Change C21 until the motor speed no

longer changes between no load and

maximum load

C22

Current limit

150 30 {%} 150

Reference: smd rated output current

• When the limit value is reached, either

the acceleration time increases or the

output frequency decreases

• When C90 = 2, max setting is 180%

C24

Accel boost

0.0 0.0 {%} 20.0 Accel boost is only active during

acceleration

smd006

This manual is related to the following products: