Commissioning, Commissioning 7 – Lenze 8400 motec Mounting Instructions User Manual
Page 61

Commissioning
7
l
61
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 5.3
7
Commissioning
Preconditions for initial switch−on
ƒ
The wiring unit is mounted and wired according to the instructions,
–
directly on a motor clamping flange or
–
with the wall adapter on a suitable surface near the motor.
ƒ
Connections with the mains, motor, holding brakes, etc. have been
established.
ƒ
The communication unit has been mounted and wired according to the
scheduled application.
–
Input and output signals
–
Safe input
–
Fieldbus
(depending on the version, only available optionally)
ƒ
If required, the basic settings for "local mode" have been carried out.
–
DIP switches
–
Potentiometer
ƒ
The drive unit has been mounted and screwed together.
ƒ
Use available control functions reasonably, e.g.
–
Inhibit controller enable
–
Set speed adjustment to the minimum setting
–
Activate safety system
ƒ
The use of a brake resistor has been checked.
–
In the case of dynamic loads or difficult control conditions, the use of the
internal brake resistor E84DZEW47R0 is always recommended for the
devices E84DGDVB4024 ... 7524 (4 ... 7.5 kW).
}
Danger!
High hazard potential during commissioning
Incorrect settings may cause unexpected and dangerous motor and
system movements.
Possible consequences:
ƒ
Damage to material assets
ƒ
Injury to persons
Protective measures:
ƒ
Clear hazardous area
ƒ
Observe safety instructions and safety clearances