Press, Ωv/a, English – Klein Tools CL3100 User Manual
Page 3: Symbols used on lcd, Electrical specifications
ENGLISH
Continuity
V
AT
0
10
20
40
30
Apro
PRESS
Ω
V/A
400V
CATIII
400V
CATIII
correct
Incorrect:
Opposing currents cancel
2. current:
< 200a ac
Continuity
V
AT
0
10
20
40
30
Apro
resistance: < 40M
Ω
3.
resistance / continuity
continuity: tone below 30
Ω
SYMBoLS USED oN LcD
~
ac Measurement
Dc Measurement
-
Negative Dc Value
Low Battery
MAX
Maximum reading
MIN
Minimum reading
AT
auto range active
AUTO
auto Function
active (V/a)
O.L.
overload: range
Exceeded
Apo
auto Power-off active
V
Voltage Measurement
A
current in amps
Ω
resistance in ohms
continuity test
m
Milli 10
-3
k
Kilo 10
3
M
Mega 10
6
ELEctrIcaL SPEcIFIcatIoNS
Dc Voltage Measurement
range
resolution
accuracy
2.1 ~ 1000V
0.001V ~ 1V
± (1.0% + 4 digits)
-1.8 ~ -1000V
0.001V ~ 1V
overload Protection:
1000V
Input Impedance:
>
10M
Ω
ac Voltage Measurement
range
resolution
accuracy
1.3 ~ 750V
0.001V ~ 1V
± (1.5% + 3 digits)
overload Protection:
750V RMS
Frequency:
45 to 400Hz
Input Impedance:
10M
Ω
response:
Averaging
ac current Measurement
range
resolution
accuracy
0.9 ~ 200A
0.1A
± (2.5% + 8 digits)
overload Protection:
200A
Frequency:
45 to 400Hz
response:
Averaging
resistance Measurement
range
resolution
accuracy
400
Ω
0.1
Ω
± (1.0% + 4 digits)
4
kΩ
0.001k
Ω
40
kΩ
0.01k
Ω
400
kΩ
0.1k
Ω
4
MΩ
0.001M
Ω
40
MΩ
0.01M
Ω
± (2.0% + 4 digits)
overload Protection:
600V
continuity test
overload Protection
open circuit Voltage
600V
Appx. 0.45V