Outputs

A/D converter

Display

Electrical data

Housing

Relay, changeover (SPDT)

- contact rating
- contact life

5A at 230V AC resistive load

350 000 operations at rated load / 750 000 operations at 1A

Logic outputs

0/12V / 25mA max. (sum of all output currents 30mA max.)

Supply voltage for
2-wire transmitter

electrically isolated, not stabilized

15.8 — 15.2V / 30 — 50mA

Relay, changeover (SPDT), option

- contact rating
- contact life

8A at 230VAC resistive load

100 000 operations at rated load / 350 000 operations at 3A

Relay, make (SPST-NO), option

- contact rating
- contact life

3A at 230VAC resistive load

350 000 operations at rated load / 900 000 operations at 1A

Solid-state relay (option)

- contact rating
- protection circuitry

1A at 230V

varistor

Voltage (option)

- output signals
- load resistance

-

accuracy

0 — 10V / 2 — 10V

R

load

 500

 0.5%

Current (option)

- output signals
- load resistance
- accuracy

0 — 20mA / 4 — 20mA

R

load

 500

 0.5%

Resolution

dynamic up to 16 Bit

Sampling cycle time

50ms, 90ms, 150ms, 250ms (configurable)

Type

LCD with background lighting

Display 1

7-segment display, 18mm high, 5 digits, color: red

Function of display 1

measurement display and parameter setting

Display 2

16-segment display, 7mm high, 8 digits, color: red/green (switchable)

Function of display 2

24-character running text display (alarms), display of measurements or parameter names

Display 3

4 switching status indicators (K1 to K4), 3mm high

Supply voltage (switch-mode PSU)

110 — 240V AC -15/+10%, 48 — 63Hz or

20—30V AC/DC, 48—63Hz

Electrical safety

to EN 61010, Part 1

overvoltage category III, pollution degree 2

Power consumption

13VA max.

Data backup

EEPROM

Electrical connection

at the back, via screw terminals,

conductor cross-section up to 2.5mm

2

(see table on page 5)

Electromagnetic compatibility (EMC)

- interference emission
- interference immunity

EN 61326-1

Class B

to industrial requirements

Housing type

plastic housing for panel mounting to IEC 61554

Depth behind panel

90 mm

Ambient/storage temperature range

0 to 55°C / -30 to +70°C

Climatic conditions

rel. humidity

90% annual mean, no condensation

Operating position

horizontal

Enclosure protection

to EN 60529, front IP65 / back IP20

Weight (fully fitted)